AIR SYSTEMS: MINIMUM VENTILATION AND VAV SYSTEM CONTROLS 23.33<br />

Similarly, when the measured CO2 concentration is � 400 ppm, the minimum outdoor intake<br />

0.07 cfm/ft 2 (0.35 L/s�m 2 ), <strong>and</strong> the remaining part is 0.07 � 0.03 � 0.04 cfm/ft 2<br />

(0.2 L/s�m 2 ) which can provide a space pressure around � 0.005 in. WG (1.25 Pag).<br />

7. During the minimum outdoor <strong>air</strong> recirculating mode, if a mixed plenum pressure control is<br />

used, either a pressure sensor located in the mixed plenum measures the static pressure difference<br />

between the mixed plenum <strong>and</strong> outdoors �pm,p, as shown in Fig. 23.4a, or a pressure sensor measures<br />

the pressure drop <strong>of</strong> the outdoor <strong>air</strong> damper <strong>and</strong> the louver, as shown in Fig. 23.4b. If the measured<br />

static pressure difference or pressure drop decreases <strong>and</strong> is less than a set point, such as � 0.4<br />

to � 0.6 in. WC (� 100 to � 150 Pa), the DDC controller closes the recirculating damper until<br />

�pm,p equals the set point <strong>and</strong> an amount <strong>of</strong> minimum outdoor <strong>air</strong> <strong>of</strong> o,sys � 0.14 cfm/ft 2 (0.7<br />

L/s� m2 V˙ o,min � V˙<br />

bv �<br />

V˙<br />

) is extracted in the AHU. The minimum outdoor <strong>air</strong> damper is opened a fixed amount, such<br />

as 100 percent.<br />

Mixed plenum pressure control provides an approximately constant minimum outdoor <strong>air</strong> with an<br />

amount <strong>of</strong> V˙ o,sys. During minimum outdoor <strong>air</strong> recirculating mode, for VAV systems with a supply<br />

<strong>and</strong> return fan combination, the minimum outdoor damper opens 100 percent, the exhaust damper<br />

opens 30 percent, <strong>and</strong> the economizer damper is closed. A space pressure sensor measures the representative<br />

space pressure pr, in in. WG (Pag). If it exceeds � 0.03 in. WG (7.5 Pag), a DDC controller<br />

increases the speed <strong>of</strong> the return fan through a variable-speed drive, <strong>and</strong> thus reduces the amount <strong>of</strong><br />

minimum outdoor <strong>air</strong> intake as well as the space pressure <strong>and</strong> maintains pr at less than � 0.03 in.<br />

WG (7.5 Pag).<br />

When the zone load reduces, the speed <strong>and</strong> volume flow <strong>of</strong> the supply fan reduce accordingly.<br />

As the measured pr drops below � 0.005 in. WG (1.25 Pag) because the return fan has not followed<br />

the supply fan to reduce its volume flow appropriately, the DDC controller then reduces the speed<br />

<strong>of</strong> the return fan, <strong>and</strong> therefore space pressure pr increases <strong>and</strong> is maintained at a value not less than<br />

� 0.005 in. WG (1.25 Pag), as discussed in Sec. 23.6.<br />

8. When the outdoor temperature 55°F � To � 75°F (12.8°C � To � 23.9°C), the AHU is operated<br />

in 100 percent outdoor <strong>air</strong> economizer cycle, as shown in Fig. 23.7b . The DDC controller<br />

opens 100 percent the minimum outdoor <strong>air</strong> damper, economizer damper, <strong>and</strong> exhaust damper. The<br />

recirculating damper is closed. When 100 percent outdoor <strong>air</strong> is used for free cooling, it overrides<br />

the minimum ventilation control.<br />

The cooling <strong>and</strong> dehumidifying capacity <strong>of</strong> the chilled water cooling coil is also required at the<br />

same time. The DDC controller modulates the opening <strong>of</strong> the two-way control valve <strong>of</strong> the cooling<br />

coil to maintain a discharge <strong>air</strong> temperature Tdis � 55°F (12.8°C).<br />

9. When the outdoor temperature To,mix � To � 55°F (12.8°C), the AHU is operated in the <strong>air</strong><br />

economizer cycle with mixed <strong>air</strong> control. Here To,mix is the outdoor <strong>air</strong> temperature at which the<br />

AHU or PU starts the mixed <strong>air</strong> control (such as To,mix � 30°F, or � 1.1°C) to provide a mixture<br />

<strong>of</strong> outdoor <strong>air</strong> <strong>and</strong> recirculating <strong>air</strong> at discharge <strong>air</strong> temperature Tdis directly, as discussed in Sec.<br />

23.7. (Refer to Fig. 23.7.) So To,mix depends on the percentage <strong>of</strong> outdoor <strong>air</strong> among the supply<br />

<strong>air</strong> <strong>and</strong> on the load ratio. In an <strong>air</strong> economizer cycle mixed <strong>air</strong> mode, a DDC controller opens 100<br />

percent the minimum outdoor <strong>air</strong> damper <strong>and</strong> exhaust damper <strong>and</strong> modulates the economizer<br />

damper <strong>and</strong> recirculating damper to maintain a mixed <strong>air</strong> temperature equal to Tdis � 55°F<br />

(12.8°C) directly.<br />

Since the amount <strong>of</strong> outdoor <strong>air</strong> intake in the AHU during mixed <strong>air</strong> mode is always greater than<br />

the amount <strong>of</strong> minimum outdoor <strong>air</strong> V˙ o,sys in recirculating mode, the mixed <strong>air</strong> control overrides the<br />

minimum ventilation control.<br />

To provide cold <strong>air</strong> supply for the interior zone even in winter, the DDC controller resets Tdis �<br />

55°F (12.8°C).<br />

10. In the perimeter zone<br />

● If the perimeter zone temperature T rxn <strong>and</strong> interior zone temperature T rin drop below 75°F<br />

(23.9°C), the terminal controller reduces the opening <strong>of</strong> the single-blade damper <strong>and</strong> thus the sup-