16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

29.12 CHAPTER TWENTY-NINE<br />

System Characteristics<br />

maximum total pressure loss in any <strong>of</strong> the branch take<strong>of</strong>fs connected to the supply main duct. And<br />

0.1 in. WG (25 Pa) should be added as a safety factor.<br />

For a supply duct system with similar configuration in branch take-<strong>of</strong>fs, the static pressure sensor<br />

<strong>of</strong> a duct static pressure control should be located near the remote end <strong>of</strong> the main duct as well<br />

as at a location where steady static pressure can be properly measured, as shown in Fig. 29.1.<br />

If there are two or three supply main ducts, two or three static pressure sensors should be installed.<br />

Each should be located near the remote end <strong>of</strong> each main duct. A comparator is used so that<br />

the DDC controller can pick the lowest static pressure as the feedback value to modulate the variable-speed<br />

drive to provide a duct static pressure higher than the preset value in all main ducts.<br />

System characteristics <strong>of</strong> a VAV cooling packaged system are listed in Table 29.1.<br />

29.6 VAV REHEAT PACKAGED SYSTEMS<br />

System Description<br />

A VAV reheat packaged system is a multizone system that uses a packaged unit with DX coil <strong>and</strong><br />

filters to condition the <strong>air</strong> <strong>and</strong> that supplies the conditioned <strong>air</strong> to various control zones in the<br />

perimeter zone <strong>of</strong> a building through reheating VAV boxes, ducts, <strong>and</strong> diffusers, <strong>and</strong> to various control<br />

zones in the interior zones through VAV boxes, ducts, <strong>and</strong> diffusers. The zone supply volume<br />

flow rate <strong>of</strong> the cold supply <strong>air</strong> is modulated to match the variation <strong>of</strong> the zone loads during partload<br />

operation.<br />

Heating provided by the reheating coil is used to <strong>of</strong>fset the zone heating load in winter in the<br />

perimeter zone as well as to prevent the zone temperature drops below a preset temperature when<br />

the zone supply volume flow rate has been reduced to the minimum setting during cooling mode<br />

part-load operation. A reheating coil is not required in the VAV boxes in the interior zone.<br />

As discussed in Sec. 21.3, for energy saving, the zone supply volume flow rate must be reduced<br />

to a minimum setting, such as 30 percent <strong>of</strong> the peak supply volume flow rate during cooling mode<br />

part-load operation before the reheating coil is energized. Figure 29.2 shows a VAV reheat packaged<br />

system with a ro<strong>of</strong>top packaged unit. The <strong>air</strong> <strong>conditioning</strong> cycle for cooling mode operation is<br />

the same as that shown in Fig. 21.5b. Usually, the same ro<strong>of</strong>top packaged unit is used to supply<br />

conditioned <strong>air</strong> to both perimeter <strong>and</strong> interior zones. However, in winter, if two packaged units are<br />

used to serve the perimeter <strong>and</strong> interior zone separately, the mixing <strong>air</strong> temperature for the perimeter<br />

zone can be raised to a higher value, to save energy.<br />

VAV reheat packaged systems are simple <strong>and</strong> effective. However, simultaneous cooling <strong>and</strong><br />

heating processes should be minimized. VAV reheat packaged systems are used in many commercial<br />

buildings.<br />

Supply Volume Flow Rate <strong>and</strong> Coil Load<br />

In a VAV reheat packaged system, the zone peak supply volume flow rate , in cfm [m3 V˙<br />

sn<br />

/(60 s)],<br />

can be calculated from Eq. (21.4) as<br />

V˙ sn �<br />

Q rsn<br />

60� sc pa(T r � T sn)<br />

(29.12)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!