16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

7.28 CHAPTER SEVEN<br />

Changeover<br />

Two Pipe or Four Pipe. In a dual-temperature water system, the water piping from the boiler or<br />

chiller to the coils <strong>and</strong> the terminals, or to various zones in a building, can be either a two-pipe system,<br />

with a supply main <strong>and</strong> a return main, as shown in Fig. 7.10a; or a four-pipe system, with a hot<br />

water supply main, a hot water return main, a chilled water supply main, <strong>and</strong> a chilled water return<br />

main, as shown in Fig. 7.10b. For a two-pipe system, it is impossible to heat <strong>and</strong> cool two different<br />

coils or terminals in the same zone simultaneously. Changeover from summer cooling mode operation<br />

to winter heating mode operation is required. A four-pipe system does not need changeover operation.<br />

Chilled <strong>and</strong> hot water can be supplied to the coils or terminals simultaneously. However, a<br />

four-pipe system requires a greater installation cost.<br />

Several decades earlier, there was also a three-pipe system with a hot water supply main, a chilled<br />

water supply main, <strong>and</strong> a common return main. ASHRAE/IESNA St<strong>and</strong>ard 90.1-1999 clearly specifies<br />

that hydronic systems that use a common return system for both hot water <strong>and</strong> chilled water shall<br />

not be used. This is because <strong>of</strong> the energy loss during the mixing <strong>of</strong> the hot <strong>and</strong> chilled water.<br />

In a dual-temperature two-pipe system, changeover refers to when the operation <strong>of</strong> one zone or the<br />

entire water system in a building changes from heating mode to cooling mode, or vice versa. During<br />

changeover, the water supplied to the terminals is changed from hot water to chilled water, or<br />

vice versa. The changeover temperature T co, °F (°C), is the outdoor temperature at which the space<br />

sensible cooling load can be absorbed <strong>and</strong> removed by the combined effect <strong>of</strong> the conditioned<br />

outdoor <strong>air</strong>, the primary <strong>air</strong>, <strong>and</strong> the space transmission <strong>and</strong> infiltration loss. Such a relationship can<br />

be expressed as:<br />

K � 60� soc pa<br />

T co � T r � �Q ris ��Q res � KV˙ so(T r � T so)<br />

q tl<br />

where Tr � space temperature, °F (°C)<br />

sum <strong>of</strong> internal sensible loads from electric lights, occupants, <strong>and</strong> appliances,<br />

Btu/h (W)<br />

sum <strong>of</strong> external sensible loads through building shell, Btu/h (W)<br />

volume flow rate <strong>and</strong> density <strong>of</strong> conditioned outdoor <strong>air</strong>, cfm (m3 /min) <strong>and</strong> lb/ft 3<br />

(kg/m 3 �Qris �<br />

�Qres �<br />

V˙<br />

so, �so �<br />

)<br />

cpa � specific heat <strong>of</strong> <strong>air</strong>, Btu/lb�°F (J/kg�°C)<br />

Tso � supply temperature <strong>of</strong> outdoor <strong>air</strong> or primary <strong>air</strong>, °F (°C)<br />

qtl � transmission <strong>and</strong> infiltration losses per 1°F <strong>of</strong> outdoor-indoor temperature difference,<br />

Btu/h�°F (W/°C)<br />

Changeover usually takes from 3 to 8 h to complete. The greater the size <strong>of</strong> the water system, the<br />

longer the changeover period. To prevent more than one changeover per day, the changeover temperature<br />

T co may have a tolerance <strong>of</strong> � 2°F (1.1°C).<br />

Changeover may cause a sudden flow <strong>of</strong> a large amount <strong>of</strong> hot water into the chiller or <strong>of</strong> chilled<br />

water into the boiler. Such a rapid change in temperature imposes a thermal shock on the chiller or<br />

boiler <strong>and</strong> may damage the equipment. For chillers, the temperature <strong>of</strong> water entering the chiller<br />

should be no higher than 80°F (26.7°C) to prevent excessive refrigerant pressure in the evaporator.<br />

For boilers, a temperature control system bypasses most <strong>of</strong> the low-temperature water until the water<br />

temperature can be gradually increased.<br />

Changeover may be performed either manually or automatically. Manual changeover is simple<br />

but may be inconvenient during periods when daily changeover is required. With sufficient<br />

safety controls, automatic changeover reduces the operating duties significantly. A compromise is<br />

(7.5)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!