16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

18.50 CHAPTER EIGHTEEN<br />

Heat Unneutralized<br />

When the supply <strong>air</strong> from the floor level is returned at the ceiling level, upward <strong>air</strong>flow lifts the heat<br />

gains in the upward flow direction <strong>and</strong> returns some heat unneutralized to the ceiling. Furthermore,<br />

the upward <strong>air</strong>flow captures most <strong>of</strong> the lighting heat gain in the return <strong>air</strong>flow. Research has<br />

demonstrated that for a typical <strong>of</strong>fice, 15 percent <strong>of</strong> space heat gain <strong>and</strong> most <strong>of</strong> ceiling-level lighting<br />

heat gain can be considered unneutralized because <strong>of</strong> the localized thermal buoyancy. In <strong>of</strong>fices<br />

where equipment is concentrated, convective plumes, upward warm exp<strong>and</strong>ing <strong>air</strong>flow above the<br />

heat sources, can capture an even greater percentage <strong>of</strong> space load by the floor-to-ceiling <strong>air</strong>flow,<br />

<strong>and</strong> results in greater capability to exhaust heat through ceiling return than the conventional space<br />

<strong>air</strong> diffusion system.<br />

Maintaining a Consistent Access Plenum Temperature<br />

Because <strong>of</strong> the smaller supply <strong>air</strong> temperature differential T r � T s in underfloor <strong>air</strong> distribution, if the<br />

underfloor plenum has hot or cold areas, the occupants’ comfort will not be satisfied by pulling <strong>air</strong> from<br />

these localized areas <strong>of</strong> temperature inconsistency. The following rules are based on test results:<br />

● Supply <strong>air</strong> colder than 63°F (17.2°C) is perceived as too cold by occupants. Blend <strong>air</strong> at the floor<br />

outlets <strong>and</strong> at other supply units.<br />

● Primary <strong>air</strong> degradation becomes unacceptable when it travels a distance exceeding 30 ft (9 m)<br />

from the point <strong>of</strong> <strong>air</strong> introduction within the access floor plenum. Provide sufficient insulated<br />

ductwork to distribute primary <strong>air</strong>.<br />

● A variation <strong>of</strong> more than 3°F (1.7°C) across a master control zone may exceed the <strong>air</strong> transfer fan<br />

adjustment range to compensate for this variation. Practical experience limits the master zoning (a<br />

zone corresponds to an area served by a VAV box or other terminals) to about 3000 ft 2 (279 m 2 ) if<br />

primary <strong>air</strong> is supplied from a central riser with VAV control, or a maximum <strong>of</strong> 10,000 ft 2<br />

(929 m 2 ) if primary <strong>air</strong> is supplied from an on-floor fan room.<br />

Floor Plenum Master Zone Air Temperature Control<br />

Design Considerations<br />

For a VAV system, as space load varies, the supply volume flow rate supply to each master control<br />

zone through an individually controlled VAV box will be varied accordingly. Because <strong>of</strong> the thermal<br />

storage effect, the floor plenum <strong>air</strong> temperature does not respond as quickly as required. It takes approximately<br />

20 min before the plenum temperature falls sufficiently to call for proper action.<br />

As the space load reduces, more recirculating <strong>air</strong> is pulled to mix with the cold primary <strong>air</strong>. The<br />

primary <strong>air</strong> rate becomes proportionally greater in the floor plenum. This effect increases the pressure<br />

on the floor plenum, <strong>and</strong> its pressure becomes positive. The pressurized cold primary <strong>air</strong> overpowers<br />

the normal downward return <strong>air</strong>flow. If a temperature sensor is located in the downward <strong>air</strong>flow<br />

path, this cold <strong>air</strong> will be sensed by the sensor, with a resulting rapid reponse to cut the<br />

primary <strong>air</strong> supply flow rate.<br />

● A structural concrete slab <strong>of</strong> 4-in. (100-mm) thickness that separates the supply raised floor<br />

plenum <strong>and</strong> the return ceiling plenum is recommended. An attempt to baffle supply <strong>and</strong> return<br />

sections <strong>and</strong> integrate them in the plenum <strong>of</strong> the same level has inherent difficulties due to <strong>air</strong><br />

leakages through plenum baffles, short-circuiting <strong>of</strong> <strong>air</strong> in the space, <strong>and</strong> limiting <strong>of</strong> the supply <strong>air</strong><br />

temperature range.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!