16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

22.18 CHAPTER TWENTY-TWO<br />

<strong>air</strong> is extracted by the supply fan to mix with the 3350 cfm (1581 L/s) <strong>of</strong> outdoor <strong>air</strong> in the mixed<br />

plenum at design volume flow. The excessive amount (350 cfm or 165 L/s) <strong>of</strong> supply <strong>air</strong> raises<br />

the space pressure until the 20,000 cfm (9438 L/s) supply <strong>air</strong> is balanced with the sum <strong>of</strong> 16,650<br />

cfm (7857 L/s) recirculating <strong>air</strong>, 3000 cfm (1416 L/s) exhaust <strong>air</strong>, <strong>and</strong> 350 cfm (165 L/s) exfiltrated<br />

<strong>air</strong> at � 0.03 in. WG (7.5 Pag) space positive pressure.<br />

● The relief fan is <strong>of</strong>ten controlled by a DDC unit controller according to the input from the space<br />

pressure sensor to maintain a space positive pressure within predetermined limits.<br />

● The main drawback <strong>of</strong> the supply <strong>and</strong> relief fan combination is the increase in pressure at the<br />

mixed plenum p m when the supply volume flow rate <strong>of</strong> a VAV system is reduced at part-load operation<br />

during minimum outdoor <strong>air</strong> recirculating mode. The higher the pressure loss <strong>of</strong> the return<br />

system, the greater the increase in p m. Higher pressure in the mixed box <strong>and</strong>, therefore, a lower<br />

�p om ( p o � p m) cause a deficiency in outdoor <strong>air</strong> intake. Various outdoor ventilation controls have<br />

been developed recently <strong>and</strong> are discussed in Chap. 23. The operation <strong>of</strong> a relief fan reduces both<br />

mixing box pressure <strong>and</strong> space pressure.<br />

22.6 SUPPLY FAN AND RETURN FAN COMBINATION<br />

Recirculation Mode<br />

Supply fan <strong>and</strong> return fan combinations are widely used, especially in <strong>air</strong> systems that serve large<br />

conditioned areas. A return fan is located upstream from the junction <strong>of</strong> the recirculating flow passage<br />

<strong>and</strong> the exhaust <strong>air</strong> passage, point ru, as shown in Fig. 22.4a. Consider an AHU or PU with a<br />

supply fan <strong>and</strong> return fan combination <strong>and</strong> an exhaust system. Its operating characteristics are the<br />

same as those in Sec. 22.4 except for the following:<br />

● A return fan is installed with the following pressure-volume characteristics:<br />

V · , cfm 10,000 15,000 20,000<br />

�p t, in. WC 1.47 1.23 1.10<br />

● The pressure loss <strong>of</strong> the exhaust damper after point ru in the exhaust passage is 0.4 in. WC (100<br />

Pa) <strong>and</strong> is 0.2 in. WC (50 Pa) for the <strong>air</strong> louver at the maximum exhaust volume flow rate. At<br />

minimum outdoor <strong>air</strong>flow, louver pressure losses can be ignored. As in the supply <strong>and</strong> relief fan<br />

combination, a minimum outdoor <strong>air</strong> damper <strong>and</strong> an economizer damper are installed, <strong>and</strong> both<br />

have a total pressure loss <strong>of</strong> 0.4 in. WC (100 Pa) at design <strong>air</strong>flow.<br />

During minimum outdoor <strong>air</strong> recirculation mode, outdoor <strong>air</strong> is drawn through the outdoor <strong>air</strong> louver,<br />

duct, <strong>and</strong> damper <strong>and</strong> is mixed with recirculating <strong>air</strong>. The mixture then flows through the filters<br />

<strong>and</strong> coils <strong>and</strong> is supplied to the conditioned space. At design volume flow, a small part is exhausted,<br />

another part is exfiltrated, <strong>and</strong> the remaining portion is extracted by the return fan flowing through<br />

the return system. At point ru, almost all the return <strong>air</strong> is recirculated through the recirculating<br />

damper.<br />

During minimum outdoor <strong>air</strong> recirculating mode, at design volume flow rate:<br />

● If the return fan is not operating <strong>and</strong> the exhaust damper is closed, then the fan total pressure <strong>of</strong><br />

the supply fan is higher than 4.65 in. WC (1156 Pa) because <strong>of</strong> the <strong>air</strong> flowing through the turned<strong>of</strong>f<br />

return fan.<br />

● If the return fan is operating, 3000 cfm (1416 L/s) <strong>of</strong> <strong>air</strong> is exhausted through the exhaust passage<br />

<strong>and</strong> exhaust damper instead <strong>of</strong> from the separate exhaust fan. The total pressure loss <strong>of</strong> the return

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!