16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

21.40 CHAPTER TWENTY-ONE<br />

● Modulates the discharge volume damper <strong>of</strong> the mixing VAV box so that the total supply volume<br />

flow rate is maintained at mixing mode setting 30 percent <strong>of</strong> the peak cold <strong>air</strong> supply V˙ scx1,d during<br />

the mixing mode operation<br />

The cold deck discharge <strong>air</strong> temperature T c,dis is still 52°F (11.1°C). If the cold <strong>air</strong> supply in the<br />

perimeter zone drops nearly to its minimum setting (30 percent <strong>of</strong> the peak supply volume flow<br />

rate), the duct <strong>and</strong> fan power heat gain may have a temperature rise <strong>of</strong> 10°F (5.6°C) which raises<br />

the cold supply <strong>air</strong> temperature in the perimeter zone to about 60°F (15.6°C).<br />

If the hot-deck discharge <strong>air</strong> temperature T h,dis cannot be maintained at a value 5°F (2.8°C)<br />

higher than the zone temperature T rxn, the DDC system controller opens the two-way valve <strong>of</strong> the<br />

hot water coil <strong>and</strong> maintains a T h,dis � T rxn � 5. And T h,dis increases as T o falls.<br />

The relationship between the outdoor <strong>air</strong> temperature T o <strong>and</strong> T h,o as well as T o <strong>and</strong> T c,o depends<br />

on the characteristics <strong>of</strong> the zone load <strong>and</strong> the construction <strong>of</strong> the building shell.<br />

6. When the outdoor <strong>air</strong> temperature T o � T c,o, the mixing VAV box is in heating mode operation.<br />

In heating mode operation, the DDC system controller positions the outdoor <strong>and</strong> recirculating<br />

dampers to provide required minimum ventilation as well as to maintain a mixture temperature <strong>of</strong><br />

50°F (10°C) if possible. The cold deck discharge <strong>air</strong> temperature remains at 52°F (11.1°C). Also the<br />

two-way valve <strong>of</strong> the water cooling coil remains closed.<br />

If the duct heat loss is about 2°F (1.1°C), the hot deck discharge <strong>air</strong> temperature is equal to<br />

T h,dis � 72 � 15 � 2 � 89°F (31.7°C). The DDC system controller modulates the two-way valve<br />

<strong>of</strong> the hot water coil in the AHU to maintain T h,dis � 89°F (31.7°C).<br />

In the mixing box X1 in the perimeter zone, the DDC terminal controller modulates the inlet<br />

mixing dampers <strong>and</strong> the discharge volume damper according to the sensed zone temperature <strong>and</strong><br />

<strong>air</strong>flow signal, to maintain a preset zone temperature <strong>of</strong> 72°F (22.2°C). As the zone heating load<br />

increases, the warm <strong>air</strong> supply volume flow rate increases accordingly to a maximum value at winter<br />

design conditions with a warm <strong>air</strong> supply temperature differential not exceeding 15°F (8.3°C).<br />

Discharge Air Temperature Control<br />

In general, the discharge <strong>air</strong> temperature from the cold deck must meet the year-round cooling requirements<br />

for the interior zone. An <strong>air</strong> economizer cycle using free cooling should be applied to<br />

the cold deck whenever possible, to meet the outdoor <strong>air</strong> requirements <strong>and</strong> to minimize <strong>refrigeration</strong><br />

in order to save energy. In the hot deck, internal heat gains carried by the recirculating <strong>air</strong><br />

should be fully utilized.<br />

Cold deck discharge <strong>air</strong> temperature T c,dis is <strong>of</strong>ten reset according to zone dem<strong>and</strong>s at part load<br />

or outdoor <strong>air</strong> temperature by means <strong>of</strong> a DDC unit controller. Hot deck discharge <strong>air</strong> temperature<br />

T h,dis is <strong>of</strong>ten reset by outdoor temperature during winter heating mode.<br />

Figure 21.11 shows the cold <strong>and</strong> warm deck discharge <strong>air</strong> temperature from the AHU <strong>of</strong> a<br />

typical dual-fan dual-duct VAV system at various outdoor temperatures. The cold deck discharge<br />

<strong>air</strong> temperature T c,dis is maintained at 52°F at all outdoor <strong>air</strong> temperatures, in order to<br />

meet high zone cooling loads in the interior zone. However, when the cold <strong>air</strong> supply volume<br />

flow rate in the perimeter zone reduces to about 30 percent <strong>of</strong> its peak volume flow during<br />

part-load operation, the temperature rise because <strong>of</strong> the fan power <strong>and</strong> duct heat gain may increase<br />

to 10°F (5.6°C), which results in a supply <strong>air</strong> temperature <strong>of</strong> cold <strong>air</strong> up to 60°F<br />

(15.6°C).<br />

When the outdoor <strong>air</strong> temperature T o drops from 70 to 60°F (21.1 to 15.6°C), the mixing <strong>of</strong> minimum<br />

outdoor <strong>air</strong> <strong>and</strong> recirculating <strong>air</strong> lowers the hot deck discharge <strong>air</strong> temperature T h,dis from 80<br />

to 76°F (26.7 to 24.4°C). If T o � 50°F (10.0°C), heating may be required in the perimeter zone, so<br />

T h,dis increases as T o falls. If the duct heat loss is 2°F (1.1°C), the warm <strong>air</strong> supply temperature differential<br />

T h,dis � 2 � T rxn should not exceed 15°F (8.3°C) even at winter design conditions, in order<br />

to avoid stratification.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!