16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

System Description<br />

AIR SYSTEMS: MINIMUM VENTILATION AND VAV SYSTEM CONTROLS 23.19<br />

systems. The following list relates parameters when �T s � 15 <strong>and</strong> 20°F except in an ice storage<br />

system in which �T s may increase up to 30°F (16.7°C). All units are in °F (°C), except the space<br />

relative humidity � r is in percent:<br />

�T s T cc �T sf T dis �T du T s T r � r<br />

15 (8.3) 55 (12.8) 2 (1.1) 57 (13.9) 3 (1.7) 60 (15.6) 75 (23.9) 50<br />

20 (11.1) 50 (10.0) 2 (1.1) 52 (11.1) 3 (1.7) 55 (12.8) 75 (23.9) 45<br />

Discharge <strong>air</strong> temperature control consists <strong>of</strong> the following control loops, as shown in Fig. 23.6a:<br />

● Economizer control loop. For a temperature <strong>air</strong> economizer control, it consists <strong>of</strong> an outdoor temperature<br />

sensor T2, a recirculating <strong>air</strong> temperature sensor T3, a DDC controller, outdoor damper<br />

actuators D1 <strong>and</strong> D2, a recirculating damper actuator D3 <strong>and</strong> a relief damper actuator D 4.<br />

● Cooling coil control loop. It consists <strong>of</strong> a discharge <strong>air</strong> temperature sensor T1, a DDC controller,<br />

<strong>and</strong> a cooling coil valve actuator V1.<br />

● Mixed <strong>air</strong> control loop. It consists <strong>of</strong> a mixed <strong>air</strong> temperature sensor T4, a DDC controller, outdoor<br />

damper actuators D1 <strong>and</strong> D2, <strong>and</strong> a recirculating damper actuator D3.<br />

● Heating coil control loop. It consists <strong>of</strong> a discharge <strong>air</strong> temperature sensor T1, a DDC controller,<br />

<strong>and</strong> a heating coil valve actuator V2.<br />

● Low-limit control loop (coil freeze protection). It consists <strong>of</strong> a temperature sensor T4, a DDC controller,<br />

<strong>and</strong> outdoor <strong>air</strong> damper actuators D1 <strong>and</strong> D2.<br />

For VAV systems, discharge <strong>air</strong> temperature control is a kind <strong>of</strong> cooling <strong>and</strong> heating capacity<br />

control so that conditioned <strong>air</strong> is discharged from an AHU or PU with a predetermined temperature<br />

<strong>and</strong> relative humidity, such as 57°F (13.9°C) <strong>and</strong> 95 percent relative humidity, <strong>and</strong> can perform the<br />

following requirements:<br />

1. Provide a kind <strong>of</strong> conditioned <strong>air</strong> for zone temperature control by varying the supply volume<br />

flow rate.<br />

2. Based on the conditions <strong>of</strong> <strong>air</strong> leaving the coil sensed by sensor T1, provide economizer control<br />

<strong>and</strong> modulate the cooling or heating capacity <strong>of</strong> the AHU or PU to maintain a predetermined T dis.<br />

3. In VAV systems, if an AHU or a PU serves both perimeter <strong>and</strong> interior zones, usually perimeter<br />

heating is provided by the heating coil installed in the reheating VAV boxes or fan-powered VAV<br />

boxes or by baseboard heating directly. In such a condition, T dis should meet the free-cooling<br />

requirement in interior zones even in winter.<br />

4. According to the outdoor temperature or system load, reset T dis to an optimum value for both<br />

effective operation <strong>and</strong> energy saving.<br />

For a cooling coil or heating coil in the AHU, the DDC controller modulates the coil valves continuously.<br />

However, in a ro<strong>of</strong>top packaged unit, <strong>refrigeration</strong> capacity is <strong>of</strong>ten adjusted by cycling<br />

the compressors on <strong>and</strong> <strong>of</strong>f in the separate refrigerant circuits <strong>of</strong> the DX coils. The capacity control<br />

<strong>of</strong> packaged units is discussed in Sec. 11.8.<br />

Most VAV systems use the <strong>air</strong> economizer or water economizer as the first-stage cooling to save<br />

energy. Cooling coil, mixed <strong>air</strong>, <strong>and</strong> heating coil control loops are operated in sequence so as to maintain<br />

a predetermined discharge <strong>air</strong> temperature while preventing simultaneous cooling <strong>and</strong> heating.<br />

For a typical AHU, the set point <strong>of</strong> the discharge <strong>air</strong> temperature at summer design conditions<br />

may be 57°F (13.9°C). To avoid sudden repeated changes in operating mode among the cooling coil<br />

<strong>and</strong> mixed <strong>air</strong> control loops, resulting in unstable operation, the set point for mixed <strong>air</strong> control is<br />

better set at 55°F (12.8°C) as shown in Fig. 23.6b.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!