16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

7.50 CHAPTER SEVEN<br />

Use <strong>of</strong> Balancing Valves<br />

Equal-percentage two-way control valves are widely used to modulate the flow rate <strong>of</strong> chilled water<br />

flowing through the coils during part-load operation. Because <strong>of</strong> the lower installation cost <strong>and</strong><br />

since <strong>of</strong>ten there is only limited space available inside the ceiling plenum, the direct-return piping<br />

system is <strong>of</strong>ten the best choice for the chilled water system in a multistory building. For a variableflow<br />

building loop using a direct-return piping arrangement, the argument concerns whether a balance<br />

valve is necessary for each branch pipe to balance the water flow according to its requirement,<br />

such as for branches CK, DJ, EH, <strong>and</strong> FG, as shown in Fig. 7.20a. If there are no balancing valves<br />

installed in the branch pipes, after the control valve balances the water flow at design load, can it<br />

still effectively adjust the amount <strong>of</strong> chilled water entering the coil as required in part-load operation.<br />

This depends mainly on the type <strong>of</strong> control valve, the control mode adopted, the variation in<br />

pressure drop between various branches, <strong>and</strong> the difference in main pipe pressure drop between the<br />

farthest <strong>and</strong> the nearest branch regardless <strong>of</strong> whether equal-percentage two-way control valve with<br />

modulation control (such as proportional plus integral control ) or two-way control valve with twoposition<br />

on/<strong>of</strong>f control (including pulse-width-adjusted two-position control) is used.<br />

For an equal-percentage two-way control valve with modulation control for many AHUs, consider<br />

a plant-building loop in a chilled water system, as shown in Fig. 7.20a. At the design load, the<br />

chilled water volume flow rate through branch FG is 80 gpm (0.30 m 3 /min), the corresponding<br />

pressure drop <strong>of</strong> its fully opened equal-percentage two-way valve is 7.5 ft WC (3.3 psi or 2.3 m<br />

WC), <strong>and</strong> the pressure drop across the farthest branch FG is 20 ft WC (8.7 psi or 6.1 m WC). From<br />

Eq. (5.8), the flow coefficient<br />

C v � V˙<br />

Usually, the difference between the pressure drop across the farthest branch from the building pump<br />

FG <strong>and</strong> the pressure drop across the nearest branch CK is <strong>of</strong>ten within 60 ft WC (26 psi or 18 m<br />

WC). At design load, for a fully opened two-way control valve in branch CK, even if all this 26 psi<br />

(18 m head loss) has been added, the chilled water volume flow rate is then<br />

From Fig. 5.16, for a typical equal-percentage two-way valve, when the percentage <strong>of</strong> the valve<br />

stem travel lies between 80 <strong>and</strong> 100 percent, the relationship between the percentage <strong>of</strong> full-range<br />

travel <strong>of</strong> valve stem z <strong>and</strong> the percentage <strong>of</strong> water flow rate when the valve is fully opened is<br />

where k � proportional constant<br />

K � flow parameter affected by size <strong>of</strong> valve<br />

Since 80/238 � 0.336, substituting into Eq. (7.17) gives<br />

0.336 � 0.004e5.5z V˙ v<br />

√�p vv<br />

� 80<br />

√3.3<br />

� 44<br />

V˙ � C v √�p vv � 44√3.3 � 26 � 238 gpm (15 L / s or 0.90 m 3 / min)<br />

� Ke kz � 0.004e 5.5 (7.17)<br />

And the percentage <strong>of</strong> full-range travel <strong>of</strong> valve stem z � 0.805. That is, an equal-percentage twoway<br />

control valve in branch CK will close its opening from 100 percent fully open to 80.5 percent<br />

for water flow balance at design load. Avery et al. (1990) emphasized that “If properly selected<br />

valves (those with equal percentage ports <strong>and</strong> with the correct actuators) are used, 20 percent or less<br />

<strong>of</strong> the stroke will be used to balance the flow. The rest <strong>of</strong> the stroke will still be available to modulate<br />

the flow within the design limits.” Rishel (1997) also stated that manual balance valves <strong>and</strong> automatic<br />

balance valves should not be used on variable-volume, direct-return, modulating type, coil<br />

control valve, chilled water systems.<br />

Therefore, an equal-percentage, two-way control valve, direct-return VAV system can balance<br />

the water flow in a direct-return chilled water system, <strong>and</strong> at least 80 percent <strong>of</strong> its stroke is still<br />

V˙ v

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!