16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

where m˙ ex,r, m˙ eu � mass flow rate <strong>of</strong> <strong>air</strong> exhausted, including <strong>air</strong> exhausted from the restroom <strong>and</strong><br />

from the AHU, lb/min (kg/min). In most conditioned space, a space positive pressure � pim is thus<br />

formed because <strong>of</strong> a surplus <strong>of</strong> outdoor <strong>air</strong> � m˙ inf entering the system, which is then exfiltrated<br />

through the gaps <strong>and</strong> openings on the building shell to outdoors <strong>and</strong> can be calculated as<br />

where � inf � volume flow rate <strong>of</strong> exfiltration, cfm (m3 /min)<br />

Ae,l � effective leakage area on building shell, ft2 (m2 )<br />

�r � space <strong>air</strong> density, lb/ft3 (kg/m 3 V˙<br />

)<br />

�pro � space <strong>and</strong> outdoor pressure difference, in. WC (Pa)<br />

(23.4)<br />

● As discussed in Sec. 20.3, the space <strong>and</strong> outdoor pressure difference <strong>of</strong>ten has a value between<br />

� 0.005 <strong>and</strong> 0.03 in. WC (1.25 <strong>and</strong> 7.5 Pa). If a pressure sensor in a space pressurization control<br />

system needs to sense a 10 percent change in p im, that is, typically � 0.0005 in. WG (0.13 Pa), it<br />

would be difficult <strong>and</strong> expensive to specify such a level <strong>of</strong> accuracy for most comfort systems.<br />

● For an average leaky one-story <strong>of</strong>fice building with an exterior wall area <strong>of</strong> 10,000 ft 2 (929 m 2 )<br />

<strong>and</strong> a floor area <strong>of</strong> 20,000 ft 2 (1858 m 2 ), as discussed in Sec. 23.2, from Eq. (20.2)<br />

From Eq. (23.4), for this average leaky <strong>of</strong>fice building, the effective leakage area is<br />

A e,l �<br />

�V˙ inf<br />

4005√�p ro<br />

Also from Eq. (23.4) the outdoor <strong>air</strong> intake required to maintain various space positive pressures<br />

<strong>and</strong> to exfiltrate them in this average leaky <strong>of</strong>fice building with 10,000 ft 2 (929 m 2 ) <strong>of</strong> exterior wall<br />

is as follows:<br />

VAV Systems Return/Relief Fan Volume Flow Control<br />

AIR SYSTEMS: MINIMUM VENTILATION AND VAV SYSTEM CONTROLS 23.17<br />

�m˙ inf ��V˙ inf� r<br />

�V˙ inf � 4005A e,l √�p ro<br />

V˙ leak � C flow A w(�p) 0.65 � 1.0(10,000)(0.3) 0.65 � 4572 cfm (2157 L / s)<br />

� 4572<br />

4005√0.3<br />

� 2.08 ft 2 (0.193 m 2 )<br />

Required outdoor <strong>air</strong> intake<br />

�pro, in. WC (Pa) Exterior wall area, cfm/ft 2 (L/s�m2 ) Floor area, cfm/ft 2 (L/s�m2 )<br />

� 0.005 0.059 (0.30) 0.0295 (0.15)<br />

� 0.01 0.083 (0.42) 0.0417 (0.21)<br />

� 0.02 0.118 (0.60) 0.059 (0.30)<br />

� 0.03 0.144 (0.73) 0.072 (0.36)<br />

� 0.05 0.186 (0.95) 0.093 (0.47)<br />

� 0.1 0.263 (1.33) 0.132 (0.67)<br />

For a VAV system with either a supply <strong>and</strong> relief fan combination as shown in Fig. 22.3, or a supply<br />

<strong>and</strong> return fan combination as shown in Figs. 22.1 <strong>and</strong> 22.4, if the volume flow rate <strong>of</strong> supply <strong>air</strong> reduces<br />

during part-load, the amount <strong>of</strong> return <strong>air</strong> extracted along points ru should be reduced accordingly<br />

in order to provide the required outdoor ventilation <strong>air</strong> <strong>and</strong> to maintain a desirable space pressure.<br />

Modulating the speed <strong>of</strong> the return/relief fan with adjustable-frequency drives, <strong>and</strong> thus its<br />

volume flow, to maintain space pressure within predetermined limits is a simple, direct, <strong>and</strong> effective<br />

means <strong>of</strong> return/relief fan volume control.<br />

Place a pressure sensor in a representative floorspace. The location <strong>of</strong> the indoor pressure sensor<br />

must be away from the door <strong>and</strong> openings to the ouside, as well as away from the elevator lobbies.<br />

The outdoor reference pressure should be typically 10 to 15 ft (3 to 4.5 m) above the building <strong>and</strong>

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!