17.20 CHAPTER SEVENTEEN<br />

TABLE 17.6 Minimum Duct Insulation R-Value, * Cooling <strong>and</strong> Heating Supply Ducts <strong>and</strong> Return Ducts<br />

Duct location<br />

Climate zone<br />

Unvented<br />

attic with<br />

Unvented<br />

attic with Indirectly<br />

Envelop Ventilated backloaded ro<strong>of</strong> Unconditioned conditioned<br />

criteria table HDD65 CDD50 Exterior attic ceiling insulation space † space § Buried<br />

Heating ducts only<br />

5-1 to 5-7 0-1800 All None None None None None None None<br />

5-8 to 5-12 1801-3600 All R-3.5 None None None None None None<br />

5-13 to 5-15 3601-5400 All R-3.5 None None None None None None<br />

5-16 to 5-18 5401-7200 All R-6 R-3.5 None None None None R-3.5<br />

Cooling only ducts<br />

5-15, 18, 20,<br />

22 to 26<br />

All 0-1800 R-1.9 R-1.9 R-1.9 R-1.9 R-1.9 None None<br />

5-12, 14, 17,<br />

19, 21<br />

All 1801-3600 R-3.5 R-1.9 R-3.5 R-1.9 R-1.9 None None<br />

5-7, 9, 11,<br />

13, 16<br />

All 3601-5400 R-3.5 R-3.5 R-6 R-1.9 R-1.9 None None<br />

5-4, 6, 8, 10 All 5401-7200 R-6 R-6 R-6 R-3.5 R-1.9 None None<br />

Combined heating <strong>and</strong> cooling ducts<br />

5-9 1801-2700 0-5400 R-6 R-3.5 R-6 R-1.9 R-1.9 None<br />

5-10 2701-3600 5401 � R-6 R-6 R-6 R-3.5 R-3.5 None<br />

5-11 2701-3600 3601-5400 R-6 R-6 R-6 R-3.5 R-3.5 None<br />

5-12 2701-3600 0-3600 R-3.5 R-3.5 R-3.5 R-1.9 R-1.9 None<br />

5-13 3601-5400 3601 � R-6 R-6 R-6 R-3.5 R-3.5 None<br />

5-14 3601-5400 1801-3600 R-6 R-3.5 R-6 R-1.9 R-3.5 None<br />

5-15 3601-5400 0-1800 R-3.5 R-3.5 R-3.5 R-1.9 R-1.9 None<br />

Return ducts<br />

5-1 to 5-26 All climates R-3.5 R-3.5 R-3.5 None None None None<br />

* Insulation R-values, measured in (h� ft 2 � °F)/Btu, are for the insulation as installed <strong>and</strong> do not include film resistance. The required minimum<br />

thicknesses do not consider water vapor transmission <strong>and</strong> possible surface condensation. Where exterior walls are used as plenum walls, wall insulation<br />

shall be as required by the most restrictive condition <strong>of</strong> 6.2.4.2 or Section 5. Insulation resistance measured on a horizontal plane in accordance<br />

with ASTM C518 at a mean temperature <strong>of</strong> 75°F at the installed thickness.<br />

† Includes crawl spaces, both ventilated <strong>and</strong> nonventilated.<br />

§ Includes return <strong>air</strong> plenums with or without exposed ro<strong>of</strong>s above.<br />

Source: ASHRAE/IESNA St<strong>and</strong>ard 90.1-1999. Reprinted by permission.<br />

do not include <strong>air</strong> film resistances. The required minimum thickness does not consider water vapor<br />

transmission <strong>and</strong> possible surface condensation. The recommended thickness <strong>of</strong> insulation layer, or<br />

duct wrap, for R-3.5 h�ft 2 �°F/Btu (0.62 m 2 �°C/W) is 1 to 1.5 in. (25 to 38 mm), <strong>and</strong> for R-6<br />

h�ft 2 �°F/Btu (1.06 m 2 �°C/W) is 2 to 3 in. (50 to 75 mm).<br />

Exceptions <strong>of</strong> duct <strong>and</strong> plenum insulation include<br />

● Factory-installed plenums, casings, <strong>and</strong> ductwork as part <strong>of</strong> the equipment<br />

● Ducts or plenums located in heated spaces, semiheated spaces, or cooled spaces<br />

● For runout less than 10 ft (3 m) in length to <strong>air</strong> terminals or <strong>air</strong> outlets, R-value <strong>of</strong> insulation need<br />

not exceed R-3.5.<br />

● Backs <strong>of</strong> <strong>air</strong> outlets <strong>and</strong> outlet plenums exposed to unconditioned or indirectly conditioned space<br />

with face area exceeding 5 ft2 (0.5 m2 ) need not exceed R-2, for those 5 ft2 (0.5 m2 ) or smaller<br />

need not be insulated.