18.36 CHAPTER EIGHTEEN<br />

FIGURE 18.22 Layout <strong>of</strong> slot diffusers for a large open <strong>of</strong>fice in Example 18.1. All dimensions in feet.<br />

Supply temperature differential 15°F (8.3°C)<br />

Sound level NC 40<br />

Cooling load density in perimeter zone 50 Btu/h� ft 2 (158 W/m 2 )<br />

Linear density <strong>of</strong> heating load 300 Btu/h� ft (288 W/m)<br />

Design a space <strong>air</strong> diffusion system for this <strong>of</strong>fice for year-round operation using a VAV system.<br />

Its minimum supply volume flow rate is 50 percent <strong>of</strong> the design volume flow at part-load operation.<br />

The ceiling plenum is used as a return plenum.<br />

Solution<br />

1. For a large, open <strong>of</strong>fice using a VAV system, a space <strong>air</strong> diffusion system <strong>of</strong> mixing <strong>air</strong>flow<br />

pattern using ceiling slot diffusers is a suitable choice because <strong>of</strong> its good surface effect <strong>and</strong> wider<br />

T 100/L (T 0.5/L) range.<br />

2. For the perimeter zone, the overhead two-way two-slot diffuser should be located on the suspended<br />

ceiling parallel to the external wall <strong>and</strong> window glass. One <strong>of</strong> the slots should discharge<br />

downward toward the window glass. The space between the slot diffusers <strong>and</strong> the window glass is<br />

1 ft (0.3 m). Another slot discharges horizontally inward from the window glass.<br />

3. In Table 18.3 the range <strong>of</strong> T 100/L for slot diffusers having ADPI � 80 percent at a load density<br />

<strong>of</strong> 50 Btu/h� ft 2 is between 0.3 <strong>and</strong> 0.95. Considering the reduction <strong>of</strong> supply volume flow rate<br />

at 50 percent load, select a T 100/L ratio around 0.7. Because the characteristic length L in the<br />

perimeter zone is L � 15 � 1 � 14 ft, the required throw for the slot diffuser in the perimeter zone