16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

where Qrs � zone sensible cooling load, Btu/h (W), <strong>and</strong> Tr, Ts � zone <strong>and</strong> supply <strong>air</strong> temperature,<br />

°F (°C). In Eq. (21.1), [m3 /(60 s)] means that in SI units, the unit should be � m3 1 V˙<br />

s<br />

�60 /s.<br />

From Eq. (20.48b), the design cooling coil load Qcc, in Btu/h (W), can be calculated as<br />

(21.2)<br />

where h m � enthalpy <strong>of</strong> the mixture <strong>of</strong> outdoor <strong>and</strong> recirculating <strong>air</strong>, Btu/lb (J/kg), <strong>and</strong> h cc �<br />

enthalpy <strong>of</strong> conditioned <strong>air</strong> leaving the cooling coil, Btu/lb (J/kg). From Eq. (20.85), the design<br />

heating coil load Q ch, in Btu/h (W), which <strong>of</strong>fsets the space heating load or sometimes maintains a<br />

setback temperature during unoccupied periods to reduce warm-up load next morning <strong>and</strong> prevent<br />

freezing, can be calculated as<br />

where T hc, T en � <strong>air</strong> temperature leaving <strong>and</strong> entering heating coil, °F (°C).<br />

Zone Temperature Control—Sequence <strong>of</strong> Operations<br />

AIR SYSTEMS: VARIABLE-AIR-VOLUME SYSTEMS 21.17<br />

Q cc � 60V˙ s� s(h m � h cc)<br />

Q ch � 60V˙ s� sc pa(T hc � T en)<br />

(21.3)<br />

Consider a single-zone VAV system using an AHU with a water cooling coil, a water heating coil,<br />

<strong>and</strong> a temperature economizer (<strong>air</strong> economizer), as shown in Fig. 21.1. The sequence <strong>of</strong> operations<br />

<strong>of</strong> this VAV system to maintain a preset zone temperature T r is as follows:<br />

1. When the AHU is in the <strong>of</strong>f position, the outdoor <strong>and</strong> exhaust dampers are closed, the two-way<br />

valves <strong>of</strong> the cooling <strong>and</strong> heating coils are also closed, <strong>and</strong> supply <strong>and</strong> return fan motors are <strong>of</strong>f.<br />

2. When the AHU is in the on position, zone temperature sensor T1 senses the zone temperature<br />

T r, sends a signal to the DDC controller, <strong>and</strong> compares it with the set point in summer <strong>of</strong> 75°F<br />

(23.9°F) in the controller. If T r > 75°F (23.9°C), the DDC controller calls for cooling—cooling<br />

mode operation. At the same time, the outdoor temperature T o is measured by the outdoor temperature<br />

sensor T2. If T o � 75°F (23.9°C) (a temperature economizer set point), the DDC controller<br />

opens the outdoor <strong>and</strong> exhaust dampers to a minimum opening position, <strong>and</strong> fully opens the recirculating<br />

damper. The DDC controller also starts supply <strong>and</strong> return fan motors with speed control<br />

via variable speed drives.<br />

3. The discharge <strong>air</strong> temperature T dis is sensed by temperature sensor T4. During cooling<br />

mode operation, if the <strong>of</strong>f-coil temperature T cc is 55°F (12.8°C), the set point <strong>of</strong> T dis � 55 � 2<br />

(fan power) � 57°F (13.9°C). When T dis � 57°F (13.9°C) is sensed by T4, the DDC controller<br />

opens <strong>and</strong> modulates the two-way valve <strong>of</strong> the water cooling coil so as to maintain T dis � 57°F<br />

(13.9°C).<br />

4. If T o � 75°F (23.9°C), using the free cooling <strong>of</strong> outdoor <strong>air</strong> is always beneficial in order to<br />

save energy. The DDC controller fully opens the outdoor <strong>and</strong> exhaust dampers <strong>and</strong>, at the same<br />

time, closes the recirculating damper. After the <strong>air</strong> economizer is energized, if T dis is still higher<br />

than 57°F (13.9°C), the DDC unit controller will open <strong>and</strong> modulate the two-way valve <strong>of</strong> the water<br />

cooling coil to maintain T dis � 57°F (13.9°C).<br />

5. Zone temperature T r is sensed by a temperature sensor T1. This signal is compared with the<br />

zone temperature set point T r,s, such as 75°F (23.9°C) in the DDC controller. If T r drops below or<br />

rises above 75°F (23.9°C), an output from the DDC controller actuates <strong>and</strong> modulates the supply<br />

fan speed, <strong>and</strong> thus the supply volume flow rate through an adjustable-frequency variable-speed<br />

drive, to maintain T r � 75°F (23.9°C). For single-zone VAV system serving a large conditioned<br />

space, several temperature sensors can be located in different areas. Either the mean value or the<br />

highest or lowest temperature can be taken as sensed input to the DDC controller.<br />

6. A pressure sensor P1 is used to sense the zone pressure �p r in the conditioned space. If �p r �<br />

0.03 in. WC (7.5 Pa), the DDC controller starts the return fan <strong>and</strong> modulates its fan speed to maintain<br />

a zone pressure �p r � 0.03 in. WC (7.5 Pa).

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!