16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

16.22 CHAPTER SIXTEEN<br />

16.22<br />

If the required supply <strong>air</strong> volume flow rate deviates from the nominal rated value in percentage,<br />

as shown below, then the cooling capacity <strong>and</strong> sensible cooling capacity can be roughly multiplied<br />

by a multiplier because <strong>of</strong> the change <strong>of</strong> the heat-transfer coefficient as follows:<br />

2. Calculate the heating coil load at the winter design condition or at the warm-up period. Determine<br />

the capacity <strong>of</strong> the gas-fired furnace, electric heater, water or steam heating coil. For a<br />

packaged heat pump, calculate the supplementary heating capacity <strong>of</strong> the gas-fired or electric<br />

heater.<br />

3. Evaluate the external total pressure loss <strong>of</strong> the duct system, terminal, <strong>and</strong> space diffusion devices<br />

(see Chaps. 17 <strong>and</strong> 18). Determine the speed <strong>of</strong> the supply fan, relief fan, exhaust fan, or return<br />

fan, such that the volume flow <strong>and</strong> the fan total pressure <strong>of</strong> the supply fan, supply fan/return<br />

fan combination is equal to or greater than the sum <strong>of</strong> the external total pressure loss <strong>and</strong> the total<br />

pressure loss in the PU.<br />

For fans for which only a fan static pressure is given, roughly a 0.4-in. WC (100-Pa) <strong>of</strong> velocity<br />

pressure can be added to the fan static pressure for purposes <strong>of</strong> rough estimation <strong>of</strong> fan total<br />

pressure.<br />

Check that the face velocity <strong>of</strong> the DX coil does not exceed 550 fpm (2.75 m/s) so that condensate<br />

will not carry over.<br />

4. For small PUs, a medium-efficiency <strong>air</strong> filter <strong>of</strong> lower pressure drop, such as a final pressure<br />

drop between 0.4 <strong>and</strong> 0.6 in. WC (100 to 150 Pa), should be selected.<br />

Example 16.1. Select an AHU or a ro<strong>of</strong>top PU for a typical floor in a commercial building with<br />

the following operating characteristics:<br />

Supply volume flow rate 16,000 cfm (7550 L/s)<br />

Cooling coil load 520,000 Btu/h or 43 tons (152,360 W)<br />

Sensible cooling coil load 364,000 Btu/h (106,650 W)<br />

Outdoor <strong>air</strong> temperature 95°F (35°C)<br />

Entering coil dry-bulb temperature 80°F (26.7°C)<br />

Entering coil wet-bulb temperature 67°F (19.4°C)<br />

External pressure drop 2.0 in. WC (500 Pa)<br />

Total pressure loss <strong>of</strong> AHU or PU 2.25 in. WC (563 Pa)<br />

For a 4-row, 12-fins/in. water-colling coil in an AHU, chilled water enters the coil at 45°F<br />

(7.2°C) <strong>and</strong> is expected to leave the coil at 55°F (12.7°C).<br />

Solution:<br />

Volume flow � 20% � 10% 0% �10% �20%<br />

Cooling capacity 0.965 0.985 1.0 1.015 1.025<br />

Sensible cooling 0.94 0.97 1.0 1.03 1.06<br />

1. Divide the supply volume flow rate by 500 fpm, that is, 16,000/500 � 32. From Tables 16.1<br />

<strong>and</strong> 16.2, select an AHU <strong>of</strong> size 30, which gives a maximum static pressure up to 8 in. WG <strong>and</strong> a<br />

face area <strong>of</strong> cooling coil <strong>of</strong> 29 ft2 . The actual face velocity <strong>of</strong> cooling coil is<br />

vcoil � 16,000<br />

� 551 fpm (2.75 m /s)<br />

29

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!