16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

(11.1°C), as shown in Fig. 21.5b. If the temperature rise from supply duct heat gain is 2°F (1.1°C),<br />

the temperature <strong>of</strong> supply <strong>air</strong> entering the reheating coil in a reheating VAV box T en is 54°F<br />

(12.2°C).<br />

One <strong>of</strong> the primary considerations in the design <strong>of</strong> warm <strong>air</strong> supply VAV systems (including<br />

VAV reheat system) at winter design conditions is the control <strong>of</strong> stratification when warm <strong>air</strong> is supplied<br />

from overhead slot <strong>and</strong> ceiling diffusers in the perimeter zone. As discussed in Sec. 18.6, it is<br />

recommended that the supply <strong>air</strong> temperature differential T r � T s not exceed 15°F (8.3°C), to prevent<br />

excessive buoyancy effects. A terminal velocity <strong>of</strong> 150 fpm (0.75 m/s) is required at the<br />

5-ft (1.5-m) level to <strong>of</strong>fset the cold draft from the external window. An even distribution <strong>of</strong> the volume<br />

flow rate <strong>of</strong> supply <strong>air</strong> between the warm <strong>air</strong>stream blowing downward toward the window<br />

glass <strong>and</strong> the warm <strong>air</strong>stream horizontally discharged toward the partition wall across from the window<br />

is preferable.<br />

At a warm <strong>air</strong> supply volume flow rate equal to 30 percent <strong>of</strong> the summer peak volume flow rate<br />

<strong>of</strong> 1.5 cfm/ft 2 (9.14 L/s�m 2 ), the space heating load per ft 2 <strong>of</strong> floor area that can be <strong>of</strong>fset by warm<br />

<strong>air</strong> supply in the perimeter zone during winter design conditions is<br />

q rh<br />

A � 0.3 � 1.5 � 60 � 0.075 � 0.243 � 15 � 7.4 Btu / h�ft2 (23.3 W / m 2 )<br />

If the depth <strong>of</strong> the perimeter zone is 15 ft (4.6 m), the heating load linear density q h,ft is<br />

q h,ft � 7.4 � 15 � 111 Btu/h�ft (107 W/m)<br />

The maximum reheating coil load for any control zone in the perimeter zone to <strong>of</strong>fset the zone heating<br />

load at winter design conditions Q chxn, in Btu/h (W), can be calculated as<br />

(21.10)<br />

where Qrhxn � space heating load for control zone n in perimeter zone, Btu/h (W)<br />

Qvenxn � ventilation load due to a 30 percent <strong>of</strong> peak volume flow <strong>of</strong> cold supply<br />

<strong>air</strong>, Btu/h (W)<br />

V˙ s,cxn � volume flow rate <strong>of</strong> cold primary <strong>air</strong> discharged to control zone from AHU <strong>of</strong> VAV<br />

reheating system, cfm [m3/(60 s)]<br />

Ten,n, Trxn � cold primary <strong>air</strong> temperature <strong>and</strong> zone temperature <strong>of</strong> control zone n, °F (°C)<br />

For a summer peak volume flow rate <strong>of</strong> 1.5 cfm/ft 2 (9.14 L/s�m 2 ) in the perimeter zone, at 30 percent<br />

<strong>of</strong> peak volume flow that means 0.3 � 1.5 � 0.45 cfm/ft 2 (2.3 L/s�m 2 ) <strong>of</strong> cold supply <strong>air</strong>.<br />

If the zone heating load linear density q h,ft is 111 Btu/h�ft (107 W/m) <strong>and</strong> the zone heating load<br />

density is 7.4 Btu/h�ft 2 , the reheating coil load for 1 ft 2 (0.0929 m 2 ) <strong>of</strong> floor area at winter design<br />

conditions can be calculated as<br />

Q chn<br />

A<br />

Q chxn � Q rhxn � Q venxn<br />

� Q rhxn � 60V˙ s, cxn� sc pa (T rxn � T en, n)<br />

� 7.4 � 60 � 0.045 � 0.075 � 0.243(72 � 54) � 7.4 � 8.9<br />

� 16.3 Btu / h�ft 2 (51.4 W / m 2 )<br />

If the AHU that serves the perimeter zone in a VAV reheat system is separated from the interior<br />

zone, <strong>and</strong> a minimum outdoor <strong>air</strong> intake <strong>of</strong> 15 percent <strong>of</strong> the peak supply volume flow rate can be<br />

set up for the perimeter zone during the winter heating mode operation, as shown in the <strong>air</strong> <strong>conditioning</strong><br />

cycle in Fig. 21.1b, the reheating coil load is then<br />

Q chn � 7.4 � 60 � 0.45 � 0.075 � 0.243(72 � 64) � 7.4 � 3.9<br />

� 11.3 Btu / h�ft 2 (35.6 W / m 2 )<br />

A saving <strong>of</strong> about 8.9 � 3.9 � 5.0 Btu/h� ft 2 (15.7 W/m 2 ) is possible.<br />

AIR SYSTEMS: VARIABLE-AIR-VOLUME SYSTEMS 21.31

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!