16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

8.26 CHAPTER EIGHT<br />

For small low-temperature hot water heating systems, an open expansion tank is usually used.<br />

For medium-size <strong>and</strong> large systems, a diaphragm tank may be more suitable. Circulating water<br />

pumps are <strong>of</strong>ten on-line pumps (circulators) with low pump head.<br />

Part-Load Operation <strong>and</strong> Control<br />

In a low-temperature hot water heating system, one <strong>of</strong> the basic part-load controls is the variation <strong>of</strong><br />

the hot water supply temperature from the boiler in response to a variation in outdoor temperature.<br />

For instance, in the midwest, a low-temperature hot water heating system has a winter design<br />

outdoor temperature T o � 0°F (� 17.8°C). At the winter design outdoor temperature, the hot water<br />

supply temperature T ws is 190°F (88°C). When the outdoor temperature drops, T ws is reset as follows:<br />

A hot water temperature sensor located at the hot water exit <strong>of</strong> the boiler, whose set point is<br />

reset by an outdoor temperature sensor, is used to control the firing rate <strong>of</strong> the boiler by means <strong>of</strong> a<br />

DDC unit. Zone control can be performed better by sensing the hot water temperature that returns<br />

from each individual loop <strong>and</strong> then modulating the control valve to vary the mass flow rate <strong>of</strong> hot<br />

water supplied to that zone through an on-line circulating pump (see Fig. 8.7).<br />

ASHRAE/IESNA St<strong>and</strong>ard 90.1-1999 specifies that a hot water system with a design heating<br />

capacity exceeding 300,000 Btu/h (88 kW) shall include controls to automatically reset to a lower<br />

hot water supply temperature according to building loads or outdoor temperature during part-load<br />

for energy saving except for systems that use variable flow to reduce pumping energy.<br />

For a low-temperature hot water heating system installed with multiple boilers, the control strategy<br />

is to decide when to turn a boiler on or <strong>of</strong>f. This optimum operation control can be accomplished<br />

by using a microprocessor-based controller that fires a st<strong>and</strong>by boiler according to a preprogrammed<br />

s<strong>of</strong>tware instruction. This strategy depends on not only the increase or reduction in heating dem<strong>and</strong><br />

but also how the operating cost <strong>of</strong> such a hot water heating system can be minimized.<br />

ASHRAE/IESNA St<strong>and</strong>ard 90.1-1999 also specifies that for a boiler plant equipped with more than<br />

one boiler, provisions shall be made so that the hot water flow in the boiler plant can be automatically<br />

reduced when a boiler is shut down.<br />

Example 8.1. A two-pipe individual-loop low-temperature hot water heating system is used to<br />

heat a factory that has a layout shown in Fig. 8.7. At winter design conditions, hot water is supplied<br />

to the heated space at a temperature <strong>of</strong> 190°F (88°C) <strong>and</strong> returns from the baseboard finned-tube<br />

heaters at a temperature <strong>of</strong> 150°F (65°C).<br />

1. If the space heating load for the largest room (facing north) is 90,000 Btu/h (26.4 kW) <strong>and</strong> for<br />

the northwest corner room is 11,000 Btu/h (3.2 kW), <strong>and</strong> if steel tubes <strong>and</strong> fins are used, determine<br />

the number <strong>of</strong> feet <strong>of</strong> finned tubing required for each <strong>of</strong> these two rooms.<br />

2. If a pressure drop <strong>of</strong> 1 ft/100 ft (1 m/100 m) <strong>of</strong> pipe is used <strong>and</strong> the hot water system is<br />

equipped with an open expansion tank, determine the diameter <strong>of</strong> the hot water supply main for<br />

these two rooms.<br />

3. Divide this hot water system into appropriate control zones, or individual loops.<br />

Solution<br />

Outdoor temperature To, °F (°C) Supply temperature Tws, °F (°C)<br />

0(�17.8) 190 (88)<br />

32 (0) 135 (57)<br />

60 (16) 85 (29)<br />

1. For the largest room, if a two-row finned-tube heater is used, then from Table 8.1, for an average<br />

hot water temperature <strong>of</strong> (190 � 150)/2 � 170°F (77°C), the heat output <strong>of</strong> each foot <strong>of</strong> two-row

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!