16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

fans, two desktop supply outlets, flexible ducts, <strong>and</strong> a control panel. Inside the mixing box, there is<br />

a variable-speed fan to extract primary <strong>air</strong> (cold conditioned <strong>air</strong> from the AHUs) either from the<br />

low-pressure floor plenum or from the supply duct in the ceiling plenum by means <strong>of</strong> connecting<br />

flexible ducts. Another fan pulls recirculating <strong>air</strong> from the knee space under the desk. The primary<br />

<strong>air</strong> <strong>and</strong> recirculating <strong>air</strong> are mixed together according to the required fractions by regulating the<br />

opening <strong>of</strong> their dampers in each <strong>of</strong> the transporting ducts. The mixture is then drawn through an<br />

electrostatic <strong>air</strong> filter. The primary <strong>air</strong> damper is never allowed to close completely, to ensure that<br />

the minimum amount <strong>of</strong> outdoor ventilation <strong>air</strong> is supplied all the time. The mixing box is hung on<br />

the back or on the corner <strong>of</strong> the desk <strong>and</strong> is connected to the two supply nozzles (outlets) on the top<br />

<strong>of</strong> the desk by flexible ducts.<br />

Two supply nozzles may be rotated 360° on the horizontal plane. They are installed with horizontal<br />

guide vanes which are adjustable � 30° in the vertical plane.<br />

Control Panel. A desktop DDC unit controller uses adjustable sliders to control the variablespeed<br />

fan <strong>and</strong> modulate the volume flow <strong>of</strong> the supply <strong>air</strong> from the nozzles. The supply <strong>air</strong> temperature<br />

is adjusted by varying the opening <strong>of</strong> the primary <strong>and</strong> recirculating dampers, <strong>and</strong> thus the ratio<br />

<strong>of</strong> primary to recirculating <strong>air</strong>. A 200-W electric radiant heating panel in the knee space is employed<br />

during winter heating. The dimming <strong>of</strong> the occupant’s task light controls the lighting luminance<br />

<strong>and</strong> a white noise generator which has a continuous frequency spectrum with equal<br />

energy/Hz over a specified frequency range.<br />

A motion detector–based occupancy sensor sends a signal to the DDC unit which shuts the<br />

desktop system <strong>of</strong>f when the workstation is unoccupied for a specified time.<br />

Operating Characteristic. Each desktop unit can provide 40 to 250 cfm (20 to 70 L/s) <strong>of</strong> supply<br />

<strong>air</strong> from the supply nozzles. Even when the two fans in the desktop unit are shut <strong>of</strong>f, 40 cfm (20<br />

L/s) <strong>of</strong> primary <strong>air</strong> will still be delivered to the conditioned space for the minimum outdoor ventilation<br />

<strong>air</strong> requirement.<br />

The maximum outlet velocity measured at the face <strong>of</strong> the 2.3- by 4-in. (58- by 100-mm) supply<br />

outlet during laboratory tests varied between 6.5 <strong>and</strong> 24.5 fps (2 <strong>and</strong> 7.5 m/s). For a typical desktop<br />

system, the primary <strong>air</strong> temperature supplied from a variable-<strong>air</strong>-volume (VAV) AHU was 55°F<br />

(12.8°C). After mixing with recirculating <strong>air</strong>, the supply <strong>air</strong> temperature from the desktop outlet<br />

was 65°F (18.3°C).<br />

The supply nozzles are 5 ft (1.52 m) wide by 30 in. (0.76 m) deep at the back corners <strong>of</strong> the<br />

desk. Air is supplied from these two nozzles toward a focus point near the center <strong>of</strong> the front edge<br />

<strong>of</strong> the desk. For isothermal <strong>air</strong> jets <strong>of</strong> horizontal supply with a volume flow <strong>of</strong> about 90 cfm<br />

(43 L/s), the average speed at the work location in front <strong>of</strong> the desk was 3.3 fps (1 m/s).<br />

Performance <strong>of</strong> Desktop Task Conditioning Systems<br />

AIR SYSTEMS: SPACE AIR DIFFUSION 18.47<br />

Based on the laboratory investigation <strong>and</strong> field-measured results, the performance <strong>of</strong> desktop task<br />

<strong>conditioning</strong> systems was summarized in Bauman et al. (1993) as follows:<br />

● The desktop unit can be controlled to produce a wide range <strong>of</strong> thermal conditions, allowing occupants<br />

the opportunity to fine-tune the local environment to their individual comfort preferences.<br />

● Under the influence <strong>of</strong> different load density <strong>of</strong> the adjacent workstation, or under a warm average<br />

room <strong>air</strong> temperature, a desktop unit is capable <strong>of</strong> being fine-tuned to maintain a nearly comfortable<br />

environment, or to maintain a temperature <strong>of</strong> 1 to 3°F (0.56 to 1.7°C) lower than that <strong>of</strong> the<br />

workstation without the desktop unit, even at relatively low supply <strong>air</strong> volume flow rates.<br />

● At the same supply volume flow rate, a larger supply nozzle was shown to deliver lower <strong>air</strong><br />

velocity than the smaller nozzle. A larger nozzle reduces the potential to produce draft while<br />

maintaining improved ventilation performance at moderate to high supply volume flow rates.<br />

● Turning <strong>of</strong>f the desktop unit whenever the workstation is unoccupied significantly reduces its energy<br />

use.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!