16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Effective Area <strong>and</strong> Flow Rates<br />

In several <strong>air</strong>flow passages connected in parallel, the effective area A e, in ft 2 (m 2 ), can be calculated as<br />

Ae � A1 � A2 � � � � � An (22.8)<br />

where A1, A2, ��� , An � <strong>air</strong>flow areas for path 1, 2, ���, n, ft2 (m2 )<br />

In <strong>air</strong>flow paths connected in series, each with a flow area A1, A2, ���, An, in ft2 (m2 ), the effective<br />

area for these <strong>air</strong>flow paths connected in series Ae can be calculated as<br />

where A � flow area or effective area, ft 2 (m 2 )<br />

�p � pressure difference across flow path or opening, in. WC (Pa)<br />

22.10 EFFECT OF AUTOMATIC SPRINKLER<br />

ON FIRE PROTECTION<br />

AIR SYSTEMS: FAN COMBINATION AND SMOKE CONTROL 22.27<br />

�1 / 2 1<br />

�� � ��<br />

A2� n<br />

(22.9)<br />

If the flow coefficient is taken as 0.65 <strong>and</strong> <strong>air</strong> density �a � 0.075 lb/ft 3 (1.2 kg/m 3 Ae ��<br />

), the <strong>air</strong> volume<br />

flow rate V˙ , in cfm, flowing through a crack, gap, or opening can be calculated as<br />

1<br />

2 A1 �<br />

1<br />

2 A2 1 / 2<br />

V˙ � 2610A(�p)<br />

(22.10)<br />

Automatic sprinkler systems are effective <strong>and</strong> reliable fire protection systems <strong>and</strong> should be<br />

installed in buildings to provide fire protection for the occupants during a building fire. Based on<br />

experimental results, Mawhinney <strong>and</strong> Tamura (1994) summarized the effect <strong>of</strong> automatic sprinklers<br />

on fire protection as follows:<br />

● For unshielded fires, automatic fire sprinklers reduced both smoke <strong>and</strong> fire hazard to negligible<br />

levels. Unshielded fire is a fire exposed to the water sprays from activated sprinklers.<br />

● For shielded fires with activated water sprays from the sprinklers, fire continues to burn at a reduced<br />

rate <strong>and</strong> to produce smoke until the fuel inside the shielded area has all burned. Concentrations<br />

<strong>of</strong> CO 2 <strong>and</strong> CO in the smoke were dangerously high. Shield fires represent fires that are<br />

shielded from the water sprays delivered by the sprinklers above because <strong>of</strong> a desk, table, or other<br />

furniture.<br />

According to experiments, shielded crib fires produced CO concentrations as high as 8 <strong>and</strong> 9<br />

percent <strong>and</strong> CO concentrations between 1.0 <strong>and</strong> 1.5 percent (10,000 <strong>and</strong> 15,000 ppm) in a multistory<br />

building. Peacock et al. (1989) indicated that a concentration <strong>of</strong> 15,000 ppm CO would<br />

present a severe life-safety hazard to any one trapped on the fire floor.<br />

● Sprinklers reduced the temperature <strong>and</strong> radiant heat from shielded fires to nonthreatening levels<br />

within the boundary <strong>of</strong> the area covered by the sprinkler system. For a sprinkler system design<br />

that meets NFPA St<strong>and</strong>ard 13 requirements, a moderate increase in ventilation to the fire floor<br />

during a building fire should not significantly increase the fire temperatures.<br />

● Buoyancy forces for shielded, sprinklered fire were almost negligible. The recommendation for<br />

the pressure difference between different smoke control zones (fire zone <strong>and</strong> adjacent zones)<br />

�p � 0.05 in. WC (12.5 Pa) in NFPA (1988) for zone smoke control design in sprinklered buildings<br />

(ceiling height � 9 ft or 2.7 m) is more than sufficient to prevent smoke movement, provided<br />

that the door to the fire floor remains closed.<br />

● Recommended practice for zone smoke control design should allow for some <strong>air</strong>flow into the<br />

st<strong>air</strong>well to prevent the spread <strong>of</strong> smoke into the st<strong>air</strong>well when the door to the fire floor is<br />

opened.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!