System Description<br />

AC SYSTEMS: PACKAGED AND DESICCANT-BASED SYSTEMS 29.33<br />

40 gr/lb), <strong>and</strong> a dew point <strong>of</strong> 43°F (6.7°C). Using conventional dew point, there is a 22°F (12.2°C)<br />

reheat <strong>and</strong> a dedicated <strong>refrigeration</strong> system.<br />

Busby (1996) reported a desiccant-based <strong>air</strong> <strong>conditioning</strong> system for a six-room operating suite at<br />

Straith Hospital, Southfield, Michigan, as shown in Fig. 29.7. The process <strong>air</strong>stream is an outdoor<br />

<strong>air</strong>stream <strong>of</strong> 7600 cfm (3586 L/s) at an inlet with a temperature <strong>of</strong> 95°F (35°C) with a humidity ratio<br />

<strong>of</strong> 0.0142 lb/lb (kg/kg or 100 gr/lb). It flows through a prefilter <strong>of</strong> medium efficiency <strong>and</strong> a water<br />

sensible cooling coil; the outdoor <strong>air</strong> is sensibly cooled to 80°F (26.7°C) <strong>and</strong> 0.0142 lb/lb<br />

(kg/kg or 100 gr/lb). Before entering the rotary desiccant dehumidifier, the process <strong>air</strong> is divided<br />

into two <strong>air</strong>streams: a dehumidified <strong>air</strong>stream <strong>and</strong> a bypass <strong>air</strong>stream. At summer design conditions,<br />

the bypass <strong>air</strong> flows through the bypass dampers at 400 cfm (189 L/s). The desiccant used in the<br />

rotary dehumidifier is titanium silica gel. After dehumidification in the rotary dehumidifier, the temperature<br />

<strong>of</strong> the process <strong>air</strong> is raised to 138°F (58.9°C) <strong>and</strong> the humidity ratio reduced to 0.005 lb/lb<br />

(kg/kg or 36 gr/lb). Both the dehumidified <strong>and</strong> bypass <strong>air</strong>streams are extracted by the supply fan,<br />

at the outlet <strong>of</strong> the supply fan, the process <strong>air</strong> temperature is increased to 140°F (60°C), <strong>and</strong> its humidity<br />

ratio is raised to 0.0057 lb/lb (kg/kg or 40 gr/lb).<br />

The process <strong>air</strong> then flows through the evaporator end <strong>of</strong> the heat pipe, <strong>and</strong> its temperature drops<br />

to 95°F (35°C). When the process <strong>air</strong> flows through a water-cooling coil, its temperature is sensibly<br />

Filter<br />

95%<br />

eff.<br />

7200 cfm<br />

53� F<br />

40 gr/lb<br />

Water<br />

cooling<br />

coil<br />

95� F<br />

40 gr/lb<br />

Heater DDC<br />

controller<br />

Humidifier<br />

Heat-pipe heat exchanger<br />

T H<br />

EA<br />

140� F<br />

40 gr/lb<br />

OA<br />

Supply<br />

fan<br />

Operating room<br />

65� F f � 50%, 46 gr/lb<br />

Gas<br />

heater<br />

138� F<br />

36 gr/lb<br />

Rotary desiccant dehumidifier<br />

Reactivated<br />

fan<br />

Chilled<br />

water<br />

80� F coil<br />

100 gr/lb<br />

FIGURE 29.7 A desiccant-based <strong>air</strong> <strong>conditioning</strong> system for a six-room operating suite at Straith Hospital,<br />

Southfield, Michigan.<br />

Filter<br />

OA<br />

95� F<br />

7600 cfm<br />

100 gr/lb