16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

23.24 CHAPTER TWENTY-THREE<br />

FIGURE 23.8 Duct static pressure control.<br />

Set Point <strong>of</strong> Duct Static Pressure <strong>and</strong> Sensor’s Location<br />

The set point <strong>of</strong> the duct static pressure should be the minimum static pressure such that when added<br />

to its associated velocity pressure, their sum—the total pressure—should overcome the maximum<br />

total pressure loss in any <strong>of</strong> the branch take<strong>of</strong>fs including VAV boxes, flexible ducts, diffusers, <strong>and</strong><br />

dynamic losses under all operating conditions. The duct static pressure is more stable than the duct<br />

total pressure in a supply main duct when the <strong>air</strong>stream is flowing. More <strong>of</strong>ten, the set point <strong>of</strong> the<br />

duct static pressure in VAV systems ranges between 0.8 <strong>and</strong> 1.5 in. WG (200 <strong>and</strong> 375 Pag)<br />

The static pressure sensor should be located in the supply main duct in a position such that the<br />

required supply volume flow rate is guaranteed for all VAV boxes with greatest energy savings during<br />

part load. The nearer to the farthest branch take<strong>of</strong>f, the greater the energy saving because �p fix<br />

is nearly minimum. For most VAV systems, the duct pressure sensor is <strong>of</strong>ten located in the main<br />

duct near the farthest branch take<strong>of</strong>f <strong>and</strong> at a location where steady static pressure can be measured.<br />

Duct static pressure control is discussed also in Sec. 29.5.<br />

Warren <strong>and</strong> Norford (1993) recommended that the duct static pressure set point be reset based<br />

on messages from each VAV box collected by a poll manager control block during operation. Such<br />

a DDC control system is complicated <strong>and</strong> expensive.<br />

ASHRAE/IESNA St<strong>and</strong>ard 90.1-1999 specifies that duct static pressure sensors used to control<br />

variable-<strong>air</strong>-volume fan operating characteristics shall be placed in a position such that the controller<br />

set point is no greater than one-third <strong>of</strong> the total design fan (supply) static pressure except for direct<br />

digital control systems with zone reset capability where the sensor may be located at the fan discharge.<br />

For a supply duct system with major duct splits, multiple sensors should be installed in each<br />

major branch to ensure static pressure can be maintained in each <strong>of</strong> the major branches.<br />

For <strong>air</strong> systems with direct digital control <strong>of</strong> individual zone VAV boxes connecting to the central<br />

system controller, the duct static pressure set point shall be reset based on the zone requiring the<br />

most pressure, that is, the set point is reset lower until one zone damper is nearly wide open.<br />

Comparison between Adjustable-Frequency Drives <strong>and</strong> Inlet Vanes<br />

In VAV systems, both adjustable-frequency variable-speed drives <strong>and</strong> inlet vanes are used to modulate<br />

the volume flow <strong>and</strong> fan total pressure <strong>of</strong> the centrifugal supply, return, relief, <strong>and</strong> exhaust fans,<br />

as described in Sec. 15.4. Generally, fans using adjustable-frequency variable-speed drive to vary

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!