16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

22.14 CHAPTER TWENTY-TWO<br />

to balance the <strong>air</strong>flow, the space pressure is changed from � 0.03 to � 0.03 in. WG (� 7.5 to � 7.5<br />

Pag), <strong>and</strong> the exfiltration changes to infiltration. The pressure loss at the outdoor <strong>air</strong> intake passage<br />

(excluding the damper), like the intake louver <strong>and</strong> duct friction loss �p lou, should be taken into<br />

account only in the outdoor <strong>air</strong> economizer cycle. During minimum outdoor <strong>air</strong> recirculating mode,<br />

�p lou should be negligible.<br />

Pressure fluctuation �p om at design flow <strong>and</strong> at 50 percent design flow causes insufficient outdoor<br />

<strong>air</strong> intake. The effect <strong>of</strong> this pressure fluctuation can be reduced by using minimum outdoor<br />

ventilation <strong>air</strong> control, as discussed in Chap. 23.<br />

22.5 SUPPLY FAN AND RELIEF FAN COMBINATION<br />

Recirculation Mode<br />

Consider an <strong>air</strong> system with a supply fan, relief fan, <strong>and</strong> exhaust fan combination, as shown in<br />

Fig. 22.3a, with the same operating characteristics as mentioned in Sec. 22.4. A relief fan is a fan<br />

that is installed in the relief flow passage (exhaust flow passage), adjacent to the recirculating flow<br />

passage leading to the mixing box, to relieve the undesirably high positive space pressure. A relief<br />

fan is different from an exhaust fan, which is <strong>of</strong>ten used to exhaust fumes <strong>and</strong> contaminated or toxic<br />

gases <strong>and</strong> to maintain a negative pressure in the space or in a localized enclosure. An axial fan is <strong>of</strong>ten<br />

used as a relief fan because <strong>of</strong> its large volume flow <strong>and</strong> smaller fan total pressure. The control<br />

systems used in such a combination are similar to those <strong>of</strong> a supply fan <strong>and</strong> exhaust fan combination,<br />

except that a relief fan control is added. The relief fan has the following pressure-volume characteristics:<br />

During minimum outdoor <strong>air</strong> recirculating mode operation, the relief fan is not operating <strong>and</strong> the<br />

relief damper is closed. Outdoor <strong>air</strong> drawn into the <strong>air</strong> system is balanced by the exhaust <strong>air</strong> <strong>and</strong> the<br />

exfiltration through the openings in the building shell. In this case, the system becomes a supply fan<br />

<strong>and</strong> exhaust fan combination, <strong>and</strong> its operating characteristics are the same as those described <strong>and</strong><br />

analyzed in Sec. 22.4.<br />

Air Economizer Mode <strong>and</strong> Design Volume Flow Rate<br />

V · , cfm 10,000 15,000 16,640 17,250<br />

�p t, in. WC 4.0 2.10 1.08 0.43<br />

In a VAV system, there are <strong>of</strong>ten two outdoor <strong>air</strong> dampers: a smaller minimum outdoor <strong>air</strong> damper<br />

<strong>and</strong> a larger economizer damper. Both dampers have a total pressure loss <strong>of</strong> 0.4 in. WC (100 Pa) at<br />

100 percent outdoor <strong>air</strong> intake. During <strong>air</strong> economizer mode with 100 percent outdoor <strong>air</strong> at the design<br />

volume flow rate, the outdoor dampers are fully opened <strong>and</strong> the recirculating damper is closed.<br />

The relief fan relieves the space <strong>air</strong> pressure <strong>and</strong> maintains it within predetermined limits. Outdoor<br />

<strong>air</strong> is extracted through the intake louver <strong>and</strong> both outdoor dampers, <strong>and</strong> flows through the filter <strong>and</strong><br />

coils. The conditioned <strong>air</strong> is then supplied to the space. A small part <strong>of</strong> the space <strong>air</strong> is exhausted,<br />

<strong>and</strong> another part is exfiltrated. The majority <strong>of</strong> space <strong>air</strong> is relieved by the relief fan through the<br />

ceiling plenum <strong>and</strong> relief passage.<br />

At design volume flow, the duct friction loss <strong>of</strong> the outdoor intake passage is negligible, <strong>and</strong> the<br />

pressure loss <strong>of</strong> the intake louver is 0.2 in. WC (50 Pa). The space pressure depends mainly on the <strong>air</strong>flow<br />

balance in the space. The variable part <strong>of</strong> the pressure loss <strong>of</strong> the supply <strong>air</strong> system is then given as<br />

�p var � 0.2 � 0.4 � 2.5 � 0.85 � 0.03 � 3.98 in. WC (990 Pa)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!