16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

23.32 CHAPTER TWENTY-THREE<br />

ble cooling load in the interior zone during part-load operation in an <strong>of</strong>fice building needs cold<br />

<strong>air</strong> supply.<br />

4. During minimum outdoor <strong>air</strong> recirculating mode, when the sensed zone temperature Trn exceeds<br />

75°F (23.9°C), DDC terminal controllers modulate the opening <strong>of</strong> single-blade dampers <strong>of</strong><br />

the reheating VAV boxes in the perimeter zones <strong>and</strong> VAV boxes in the interior zones, to increase the<br />

zone, volume flow <strong>of</strong> supply <strong>air</strong> to maintain a nearly constant zone temperature Trn � 75°F<br />

(23.9°C). During part-load operation, when Trn drops below 75°F (23.9°C), because <strong>of</strong> a reduction<br />

in zone sensible cooling loads, DDC terminal controllers modulate the opening <strong>of</strong> single-blade<br />

dampers <strong>of</strong> the reheating VAV boxes in the perimeter zones <strong>and</strong> VAV boxes in the interior zones, to<br />

reduce the volume flow <strong>of</strong> the zone supply <strong>air</strong> to maintain a nearly constant zone temperature <strong>of</strong><br />

75°F (23.9°C), as discussed in Sec. 21.3.<br />

5. During minimum outdoor <strong>air</strong> recirculating mode part-load operation, when reheating VAV<br />

boxes <strong>and</strong> VAV boxes close their single-blade dampers to smaller openings, the pressure drop<br />

across the dampers increases. This results in a higher static pressure in the supply main duct. As<br />

such, an increase in duct static pressure is sensed by a pressure sensor located at a distance <strong>of</strong><br />

0.3Lmain from the farthest branch take<strong>of</strong>f in the supply main duct, as discussed in Sec. 23.8; a DDC<br />

controller modulates <strong>and</strong> reduces the speed <strong>of</strong> the supply fan through an adjustable-frequency<br />

variable-speed drive to maintain a nearly constant duct static pressure set point, such as 1.2 in.<br />

WG (300 Pag), at the location <strong>of</strong> the duct static pressure sensor. Therefore, the volume flow rate <strong>of</strong><br />

the supply fan is reduced to balance the reduction <strong>of</strong> zone supply volume flow rate during part<br />

load.<br />

6. During the minimum outdoor <strong>air</strong> recirculating mode, if CO2-based dem<strong>and</strong>-controlled ventilation<br />

is used, the relationship between the supply flow density <strong>of</strong> minimum outdoor <strong>air</strong> (as well as<br />

the corresponding minimum outdoor damper opening) <strong>and</strong> the CO2 concentration in the return duct<br />

(refer to Fig. 23.2) has already been determined during commissioning. Since as the supply fan is<br />

modulated at a speed to maintain a preset duct static pressure <strong>of</strong> 1.2 in. WG (300 Pag), the DDC<br />

controller opens the minimum outdoor damper to a setting to provide base ventilation V˙ bv first. Ac-<br />

cording to the measured CO 2 concentration in the return duct, the DDC controller then resets the<br />

minimum outdoor damper opening setting according to the determined relationship at a predetermined<br />

time interval (such as 2 <strong>and</strong> 5 min).<br />

Measured CO2 concentration, ppm Required minimum outdoor <strong>air</strong>, cfm/ft 2 (L/s�m2 )<br />

� 800 V · � 400<br />

o,sys � 0.14 (0.7)<br />

V · bv � 0.07 (0.35)<br />

The recirculating damper opens 100 percent, <strong>and</strong> the exhaust dampers open 30 percent.<br />

For a VAV system with a supply <strong>and</strong> return fan combination, a pressure sensor is used to measure<br />

the representative space pressure pr, in in. WG (Pag), <strong>and</strong> controls the space pressure in floating<br />

control mode. Only when pr � 0.03 in. WG (� 7.5 Pag) does the DDC controller increase the<br />

speed <strong>of</strong> the return fan, which raises the amount <strong>of</strong> exhaust <strong>air</strong> through the exhaust damper eu <strong>and</strong><br />

maintains pr ��0.03 in. WG (7.5 Pag). Also only when pr ��0.005 in. WG will the DDC controller<br />

reduce the speed <strong>of</strong> the return fan to increase space pressure to � 0.005 � pr � � 0.03 in.<br />

WG (� 1.25 � pr � 7.5 Pag).<br />

When the measured return duct CO2 concentration is � 800 ppm, the minimum outdoor <strong>air</strong> intake<br />

for a typical <strong>of</strong>fice building should be 0.14 cfm/ft 2 (0.7 L/s�m 2 ). Minus the exhaust through<br />

the restroom <strong>of</strong> 0.03 cfm/ft 2 (0.15 L/s�m 2 ), the remaining part is 0.14 � 0.03 � 0.11 cfm/ft 2<br />

(0.55 L/s�m 2 ). Such an amount <strong>of</strong> outdoor <strong>air</strong> is sufficient to maintain a space pressure <strong>of</strong> � 0.005<br />

� pr ��0.03 in. WG (� 0.005 � pr � � 7.5 Pag) <strong>and</strong> an associated exfiltration from an average<br />

leaky building as well as an amount <strong>of</strong> 0.015 cfm/ft 2 (L/s�m2 V˙<br />

) <strong>of</strong> exhaust <strong>air</strong> through the exhaust<br />

damper.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!