16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

10.44 CHAPTER TEN<br />

electric power input to the tower fans is approximately 10 percent <strong>of</strong> the power input to the centrifugal<br />

compressors; <strong>and</strong> the power input to the circulating pumps for condenser water is about 2 to<br />

5 percent <strong>of</strong> the power input to the centrifugal compressors.<br />

One earlier strategy for capacity control <strong>of</strong> cooling towers during part-load operation is to maintain<br />

a fixed temperature T tl for condenser water leaving the tower. This strategy does not minimize<br />

the sum <strong>of</strong> power input to the compressors, tower fans, <strong>and</strong> circulating pumps when both T tl <strong>and</strong> the<br />

condensing temperature can be lowered. When T o� falls, a lower condenser water temperature leaving<br />

the tower T tl <strong>and</strong> entering the water-cooled condenser is always energy-saving, except when low<br />

T tl causes a low condensing pressure which cannot provide effective operation <strong>of</strong> the <strong>refrigeration</strong><br />

system refrigerant flow from the condenser <strong>and</strong> evaporator <strong>and</strong> the required evaporation (<strong>refrigeration</strong><br />

effect) in the evaporator.<br />

In ASHRAE Journal (no. 3, 1997), “The HVAC&R ‘Evolution’ Continues,” it was reported that<br />

a centrifugal chiller operated with an entering condenser water temperature <strong>of</strong> 55°F (12.8°C), a<br />

minimum entering condenser water temperature. A better strategy <strong>of</strong> capacity control <strong>of</strong> cooling<br />

towers for water-cooled condensers in a centrifugal chiller is to lower T tl until T tl falls to a limit, the<br />

minimum entering condenser water temperature T con, m. If T tl falls below this limit, the <strong>refrigeration</strong><br />

system cannot be effectively operated.<br />

Most tower fans in current use are two- or three-speed fans. The key points for a nearly optimum<br />

control <strong>of</strong> cooling towers, according to Braun <strong>and</strong> Diderrich (1990), are as follows:<br />

● Use sequencing <strong>of</strong> tower fans to maintain a possibly lowered Ttl � Tcon, min during part-load operation<br />

to minimize the sum <strong>of</strong> power input to the compressors <strong>and</strong> tower fans.<br />

● Heat rejection Qrej, p determines the sequencing <strong>of</strong> tower fans, <strong>and</strong> Qrej, p, is measured by the product<br />

<strong>of</strong> the range <strong>and</strong> the water circulation rate.<br />

● Establish a simple relationship between the tower capacity <strong>and</strong> the sequencing <strong>of</strong> the tower fan.<br />

● Use an open-loop control (see Chap. 5) for a stable operation.<br />

● When an increase <strong>of</strong> tower capacity is required, the speed <strong>of</strong> tower fan operated at the lowest<br />

speed should be raised first. Similarly, during a decrease <strong>of</strong> tower capacity, the highest tower fan<br />

speed should be the first one to be reduced.<br />

● The speed <strong>of</strong> the tower fan should not be reduced in sequence to maintain a T tl lower than T con, min.<br />

Example 10.2. A counterflow induced-draft cooling tower is required to cool the condenser water<br />

from 95 to 85°F (35 to 29.4°C) at a design outdoor wet-bulb temperature <strong>of</strong> 78°F (25.6°C). If the<br />

water-<strong>air</strong> ratio <strong>of</strong> this tower is 1.2, do the following:<br />

1. Calculate the tower coefficient at this design wet-bulb temperature.<br />

2. If the outdoor wet-bulb temperature, water circulation rate, <strong>and</strong> <strong>air</strong>flow rate remain the same as<br />

in the design conditions, calculate the condenser water entering <strong>and</strong> leaving the tower if the rate<br />

<strong>of</strong> heat rejection at the water-cooled condenser has fallen to 50 percent <strong>of</strong> its design value.<br />

Take the specific heat for water as c pw � 1 Btu/lb�°F (4187 J/kg�°C).<br />

Solution. To find the enthalpy <strong>of</strong> saturated <strong>air</strong> film h s, the enthalpy <strong>of</strong> ambient <strong>air</strong> h a, <strong>and</strong> the<br />

driving potentials h s � h a, do these calculations:<br />

● Divide the temperature range <strong>of</strong> condenser water into 1°F (0.56°C) divisions such as 85, 86, ...,<br />

93, 94, 95°F. From App. Table B.1, the enthalpy <strong>of</strong> the saturated <strong>air</strong> film that surrounds the water<br />

droplets h s at various temperatures can be determined.<br />

● Find the enthalpies <strong>of</strong> the <strong>air</strong> that contacts with the condenser water at various temperatures h a by<br />

means <strong>of</strong> Eq. (10.22), starting with incoming <strong>air</strong> at a wet-bulb T o��78°F (25.6°C) in contact<br />

with the coldest condenser water at temperature 85°F (29.4°C).<br />

Based on Eq. (10.26), the tower coefficient or fill surface area required to cool the condenser<br />

water from 86 to 85°F <strong>and</strong> raise the <strong>air</strong> enthalpy from that at T o��78°F to h a78 � 1.2 is

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!