Action <strong>and</strong> Measures<br />

REFRIGERANTS, REFRIGERATION CYCLES, AND REFRIGERATION SYSTEMS 9.11<br />

3.1 percent in the Copenhagen amendments. The Copenhagen amendments had been ratified by 58<br />

parties.<br />

The impact <strong>of</strong> CFCs on the ozone layer poses a serious threat to human survival. The following<br />

measures are essential:<br />

Conversions <strong>and</strong> Replacements. Use alternative refrigerants (substitutes) to replace the CFCs in<br />

existing chillers <strong>and</strong> direct-expansion (DX) systems. During the conversion <strong>of</strong> the CFC to<br />

non–ozone depletion alternative refrigerants, careful analysis should be conducted <strong>of</strong> capacity, efficiency,<br />

oil miscibility, <strong>and</strong> compatibility with existing materials after conversion. For many <strong>refrigeration</strong><br />

systems that already have a service life <strong>of</strong> more than 15 years, it may be cost-effective to<br />

buy a new one using non-CFC refrigerant to replace the existing <strong>refrigeration</strong> package.<br />

● HFC-134a <strong>and</strong> HCFC-22 are alternative refrigerants to replace CFC-12.<br />

● HCFC-123, <strong>and</strong> HFC-245ca are alternative refrigerants to replace CFC-11 in large chillers.<br />

It is important to realize that HCFC-123 <strong>and</strong> HCFC-22 themselves are interim refrigerants <strong>and</strong> will<br />

be restricted in consumption beginning in 2004. HCFC-123 has a very low global warming potential <strong>and</strong><br />

is widely used in centrifugal chillers. HCFC-22 is widely used in small <strong>and</strong> medium-size DX systems.<br />

● HFC-134a, HFC-407C, <strong>and</strong> HFC-410A are alternative refrigerants to replace HCFC-22. HFC-<br />

407C is a near-azeotropic refrigerant <strong>of</strong> HFC-32/HFC-125/HFC-134a (23/25/52) [means<br />

(23%/25%/525)], <strong>and</strong> HFC-410A also a near-azeotropic refrigerant <strong>of</strong> HFC-32/HFC-125 (50/50).<br />

● HFC-245ca or another new HFC possibly developed before 2004 will be the hopeful alternative<br />

to replace HCFC-123.<br />

In supermarkets, CFC-502 is a blend <strong>of</strong> HCFC-22/CFC-115 (48.8/51.2).<br />

● HFC-404A, HFC-507, <strong>and</strong> HFC-410A are alternative refrigerants to replace CFC-502. HFC-<br />

404A is a near-azeotropic refrigerant <strong>of</strong> HFC-125/HFC-143a/HFC-134a(44/52/4); <strong>and</strong> HFC-<br />

507 is an azeotropic refrigerant <strong>of</strong> HFC-125/HFC-143a (45/55).<br />

Reducing Leakage <strong>and</strong> Preventing Deliberate Venting. To reduce the leakage <strong>of</strong> refrigerant from<br />

joints <strong>and</strong> rupture <strong>of</strong> the <strong>refrigeration</strong> system, one must detect the possible leakage, tighten the<br />

chillers, improve the quality <strong>of</strong> sealing material, <strong>and</strong> implement preventive maintenance.<br />

Prevent the deliberate venting <strong>of</strong> CFCs <strong>and</strong> HCFCs <strong>and</strong> other refrigerants during manufacturing,<br />

installation, operation, service, <strong>and</strong> disposal <strong>of</strong> the products using refrigerants.<br />

Avoid CFC <strong>and</strong> HCFC emissions through recovery, recycle, <strong>and</strong> reclaiming. According to<br />

ASHRAE Guideline 3-1990, recovery is the removal <strong>of</strong> refrigerant from a system <strong>and</strong> storage in an<br />

external container. Recycle involves cleaning the refrigerant for reuse by means <strong>of</strong> an oil separator<br />

<strong>and</strong> filter dryer. In reclamation, refrigerant is reprocessed for new product specifications.<br />

To avoid the venting <strong>of</strong> CFCs <strong>and</strong> HCFCs <strong>and</strong> other refrigerants, an important step is to use an<br />

ARI-certified, portable refrigerant recovering/recycling unit to recover all the liquid <strong>and</strong> remaining<br />

vapor from a chiller or other <strong>refrigeration</strong> system. An outside recovery/reclaiming service firm may<br />

also be employed. A typical refrigerant recovery unit is shown in Fig. 9.2. It includes a recovery<br />

cylinder, a vacuum pump or compressor, a water-cooled condenser, a sight glass, a shut<strong>of</strong>f float<br />

switch, necessary accessories, pipes, <strong>and</strong> hoses.<br />

To recover refrigerant from a chiller that has been shut down involves two phases: liquid recovery<br />

<strong>and</strong> vapor recovery. Liquid recovery is shown in Fig. 9.2a. The vacuum pump or compressor<br />

in the recovery unit creates a low pressure in the recovery cylinder. Liquid refrigerant is then<br />

extracted from the bottom <strong>of</strong> the chiller into the recovery cylinder. If the recovery cylinder is not<br />

large enough, the shut<strong>of</strong>f float switch ceases to operate the vacuum pump or compressor when the