16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

For water-cooled centrifugal chillers with hermetic compressors, manufacturers’ products that<br />

are currently available have a cooling capacity <strong>of</strong> 150 to 2000 tons (527 to 7032 kW). For watercooled<br />

centrifugal chillers with open compressors, the cooling capacity varies from 150 to 10,000<br />

tons (527 to 35,160 kW).<br />

For hermetic compressors using vaporized liquid refrigerant to cool the motor, no additional<br />

motor cooling system is required. Leakage <strong>of</strong> refrigerant from the bearing seals is also less than that<br />

in the open compressor. Its main drawback is that 2 to 4 percent <strong>of</strong> the liquid refrigerant must be<br />

used to cool the motor. Its cooling capacity is reduced, <strong>and</strong> its energy use is increased.<br />

Unfortunately, the IPLV in ARI St<strong>and</strong>ard 550/590-98 is developed to represent the average partload<br />

efficiency <strong>of</strong> <strong>of</strong> a single chiller. Most <strong>of</strong> the chillers are used in multichiller operation. Actual<br />

multichiller operation is different from the single-chiller operation.<br />

13.3 CENTRIFUGAL CHILLERS INCORPORATING<br />

HEAT RECOVERY<br />

System Description<br />

Operating Modes<br />

REFRIGERATION SYSTEMS: CENTRIFUGAL 13.9<br />

Many large commercial applications <strong>of</strong>ten require heating in the perimeter zone but cooling in the<br />

interior zone during the winter. If the building is considered as a whole, a heat recovery system can<br />

be used to transfer the internal heat from the interior zone to the perimeter zone to <strong>of</strong>fset the winter<br />

heating load there.<br />

A typical centrifugal chiller incorporating a heat recovery system using a double-bundle condenser<br />

is presented in Fig. 13.5. In a double-bundle condenser, water tubes are classified as tower<br />

bundles <strong>and</strong> heating bundles. Heat rejected in the condenser may be either discharged into the<br />

atmosphere through the tower bundle <strong>and</strong> cooling tower or used for heating in the coils <strong>of</strong> the perimeter<br />

zones through the heating bundle. The tower bundle may be enclosed in the same shell with the<br />

heating bundle, as shown in Fig. 13.5b, but separate plates are needed to divide the water circuits.<br />

A storage tank stores the excessive hot water from the heating bundle when the building is occupied.<br />

Hot water is then used for heating in the perimeter zone when the building is either occupied<br />

or unoccupied. A supplementary heater using, e.g., electric power may be used to raise the temperature<br />

<strong>of</strong> the hot water from the heating bundle, if necessary. A tower bypass line is always used to<br />

maintain the condenser water entering the condenser at a required value.<br />

Instead <strong>of</strong> a double-bundle condenser, an auxiliary condenser plus a st<strong>and</strong>ard condenser can be<br />

used, as shown in Fig. 13.6. Hot gaseous refrigerant is forced to either the st<strong>and</strong>ard or the auxiliary<br />

condenser after it is discharged from the compressor. When heating is required in the perimeter<br />

zone, the auxiliary condenser pump is energized, <strong>and</strong> the tower bypass three-way valve bypasses<br />

part <strong>of</strong> or all the condenser water returning to the st<strong>and</strong>ard condenser. Because the water returning<br />

from the perimeter zone <strong>and</strong> entering the auxiliary condenser is colder than that entering the st<strong>and</strong>ard<br />

condenser due to the heating load in the perimeter zone, the auxiliary condenser tube bundle<br />

has a lower temperature <strong>and</strong> attracts the hot gas from the compressor. The auxiliary condenser recovers<br />

as much heat as it can allow. The remaining rejected heat goes to the st<strong>and</strong>ard condenser <strong>and</strong><br />

is rejected to the atmosphere through the cooling tower. A balance <strong>of</strong> heat rejection between these<br />

two condensers automatically holds.<br />

A hot water bypass should be included if an auxiliary condenser is used, as shown in Fig. 13.5.<br />

Such a bypass ensures that water will not circulate through the auxiliary condenser when the chiller<br />

is deenergized. In Fig. 13.5a, the hot water pump P2 is energized only when the compressor <strong>of</strong> the<br />

centrifugal chiller is in operation.<br />

Depending on whether heating is required in the perimeter zone, the operating modes <strong>of</strong> a centrifugal<br />

chiller that is incorporated with a heat recovery system in a building with perimeter <strong>and</strong> interior

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!