REFRIGERATION SYSTEMS: RECIPROCATING, ROTARY, SCROLL, AND SCREW 11.19<br />

TABLE 11.4 Minimum Refrigeration Load for Oil Entrainment up Suction Risers <strong>of</strong> Type L Copper Tubing, in Tons<br />

1. From Table 11.1, for a suction temperature <strong>of</strong> 45°F (7.2°C) <strong>and</strong> a condensing temperature <strong>of</strong><br />

115°F (46.1°C), Fsuc,s is 1.10 <strong>and</strong> Fsuc,c � 0.93. The corrected <strong>refrigeration</strong> load Qrl for the suction<br />

line is therefore 20/(1.1 � 0.93) � 19.6 tons (68.7 kW).<br />

2. Assume an equivalent length <strong>of</strong> the suction line Leq <strong>of</strong> 90 ft (27 m). From Fig. 11.10, for a<br />

<strong>refrigeration</strong> load <strong>of</strong> 19.7 tons <strong>and</strong> Leq � 90 ft (27 m), the next-higher value <strong>of</strong> the tentative outside<br />

diameter <strong>of</strong> the suction line is in. (54 mm), a nominal diameter <strong>of</strong> 2 in. (50 mm).<br />

3. Recalculate the equivalent length, based on a copper tubing outside diameter <strong>of</strong> 2 in. (54 mm).<br />

The pressure drops <strong>of</strong> the refrigerant piping fittings <strong>and</strong> the accessories expressed as equivalent<br />

length <strong>of</strong> pipe are listed in Table 11.2. The calculated total equivalent length Leq is<br />

1 2<br />

�8 1�8 10 short radius elbows 10 � 5 � 50 ft (15 m)<br />

1 angle valve 1 � 24 � 24 ft (7.2 m)<br />

Measured length <strong>of</strong> pipe 30 ft (9 m)<br />

Total 104 ft (31.2 m)<br />

Pipe OD, in.<br />

Suction<br />

0.500 0.625 0.750 0.875 1.123 1.375 1.625 2.125 2.625 3.125 3.625 4.125<br />

Saturated gas Area, in. 2<br />

temperature, temperature,<br />

Refrigerant °F °F 0.146 0.233 0.348 0.484 0.825 1.256 1.780 3.094 4.770 6.812 9.213 11.970<br />

HCFC-22 �40.0 �30.0 0.067 0.119 0.197 0.298 0.580 0.981 1.52 3.03 5.20 8.12 11.8 16.4<br />

�10.0 0.065 0.117 0.194 0.292 0.570 0.963 1.49 2.97 5.11 7.97 11.6 16.1<br />

10.0 0.066 0.118 0.195 0.295 0.575 0.972 1.50 3.00 5.15 8.04 11.7 16.3<br />

�20.0 �10.0 0.087 0.156 0.258 0.389 0.758 1.28 1.98 3.96 6.80 10.6 15.5 21.5<br />

10.0 0.085 0.153 0.253 0.362 0.744 1.26 1.95 3.88 6.67 10.4 15.2 21.1<br />

30.0 0.086 0.154 0.254 0.383 0.747 1.26 1.95 3.90 6.69 10.4 15.2 21.1<br />

0.0 10.0 0.111 0.199 0.328 0.496 0.986 1.63 2.53 5.04 8.66 13.5 19.7 27.4<br />

30.0 0.108 0.194 0.320 0.484 0.942 1.59 2.46 4.92 8.45 13.2 19.2 26.7<br />

50.0 0.109 0.195 0.322 0.486 0.946 1.60 2.47 4.94 8.48 13.2 19.3 26.8<br />

20.0 30.0 0.136 0.244 0.403 0.608 1.18 2.00 3.10 6.18 10.6 16.6 24.2 33.5<br />

50.0 0.135 0.242 0.399 0.603 1.17 1.99 3.07 6.13 10.5 16.4 24.0 33.3<br />

70.0 0.135 0.242 0.400 0.605 1.18 1.99 3.08 6.15 10.6 16.5 24.0 33.3<br />

40.0 50.0 0.167 0.300 0.495 0.748 1.46 2.46 3.81 7.60 13.1 20.4 29.7 41.3<br />

70.0 0.165 0.296 0.488 0.737 1.44 2.43 3.75 7.49 12.9 20.1 29.3 40.7<br />

90.0 0.165 0.296 0.488 0.738 1.44 2.43 3.76 7.50 12.9 20.1 29.3 40.7<br />

Note: The capacity in tons is based on 90°F liquid temperature <strong>and</strong> superheat as indicated by the listed temperatures. For other liquid line temperatures,<br />

use correction factors in the table below.<br />

Liquid temperature, °F<br />

Refrigerant 50 60 70 80 100 110 120 130 140<br />

HCFC-22 1.17 1.14 1.10 1.06 0.98 0.94 0.89 0.85 0.80<br />

Source: ASHRAE <strong>H<strong>and</strong>book</strong> 1998, Refrigeration Systems <strong>and</strong> Applications.<br />

Reprinted with permission.<br />

4. From the capacity-Leq chart, at Qrl � 19.7 tons (68.7 kW) <strong>and</strong> Leq � 104 ft (31.2 m), the diameter<br />

<strong>of</strong> copper tubing is the same as the tentative diameter in. (54 mm). Consequently, 2 in.<br />

(54 mm) should be the size <strong>of</strong> the suction line.<br />