16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

30.12 CHAPTER THIRTY<br />

Case Study: A Fan-Powered VAV Central System<br />

A fan-powered VAV central system was designed <strong>and</strong> constructed for the 34-story <strong>of</strong>fice building <strong>of</strong><br />

the Taipei World Trade Center, Taipei, Taiwan. It has a gross floor space <strong>of</strong> 1.05 million ft 2 (97,580<br />

m 2 ) <strong>and</strong> a total <strong>air</strong> conditioned floor space <strong>of</strong> 880,310 ft 2 (81,810 m 2 ). The peak <strong>refrigeration</strong> load <strong>of</strong><br />

the building is about 2530 tons (8890 kW). The local utility rate structure strongly favors the use <strong>of</strong><br />

the <strong>refrigeration</strong> system during <strong>of</strong>f-peak hours. This project won first place in the 1991 ASHRAE<br />

Technology Awards for HVAC&R system designs for commercial buildings. The entrants were<br />

Hsing-Chung Yu <strong>and</strong> Carl E. Claus.<br />

Refrigeration System. The ice storage system was a partial storage one (ice storage systems are<br />

discussed in the next chapter). A separate flooded liquid cooler was connected to the screw compressors<br />

to provide direct cooling during on-peak hours as well as during after-hours operation, to<br />

<strong>of</strong>fset the significant nighttime load. During direct cooling, the compressors were controlled to operate<br />

at a higher suction temperature <strong>of</strong> 33°F (0.56°C) to conserve energy.<br />

A liquid overfeed system was used instead <strong>of</strong> direct expansion during the ice-making period<br />

because <strong>of</strong> its higher heat transfer. About 20 percent <strong>of</strong> the refrigerant coil surface in the ice<br />

builders could be saved. During ice melting, chilled water was supplied directly through a closedloop<br />

water circuit to the storage tanks, <strong>and</strong> the tanks were pressurized. Such an arrangement obviates<br />

the use <strong>of</strong> a heat exchanger <strong>and</strong> thus avoids the corresponding chilled water temperature<br />

rise.<br />

Condensing heat was efficiently rejected through evaporatively cooled condensers.<br />

Air Systems. Because <strong>of</strong> the lower chilled water temperature from the storage tank during ice<br />

melting, cold primary <strong>air</strong> at 45°F (7.2°C) was introduced at the parallel fan-powered unit. It was<br />

mixed with the induced plenum <strong>air</strong> to produce a supply <strong>air</strong> <strong>of</strong> 56°F (13.3°C) at the diffuser. Such a<br />

lower primary <strong>air</strong> temperature had the following consequences:<br />

● Summer space relative humidity dropped to 40 to 45 percent. The thermal comfort <strong>of</strong> the occupants<br />

was greatly improved.<br />

● Cold primary <strong>air</strong> volume flow rate was reduced to 40 percent compared with conventional <strong>air</strong> distribution.<br />

Two built-up centralized AHUs were installed in the basement. Each was used to supply 200,000<br />

cfm (94,380 L/s) <strong>of</strong> primary <strong>air</strong> from the bottom to the top <strong>of</strong> the entire building. Compared with<br />

the originally proposed conventional system with additional equipment floors at mid-level, this <strong>air</strong><br />

distribution system saved considerable rental space.<br />

The centralized <strong>air</strong> system, having floor-by-floor automatic shut<strong>of</strong>f dampers, was closely<br />

matched with the ro<strong>of</strong>-mounted smoke control system. In case <strong>of</strong> a building fire, the return fan<br />

would be stopped <strong>and</strong> the ro<strong>of</strong>top exhaust fan would be started to purge the smoke from the fire<br />

floor through the opening <strong>and</strong> closing <strong>of</strong> dampers connected to the smoke exhaust system. At the<br />

same time, <strong>air</strong> would be supplied to the two floors above the fire floor as well as one floor below to<br />

pressurize these floors.<br />

The <strong>air</strong> system also did the following:<br />

● Provided 15 cfm (7.1 L/s) <strong>of</strong> outdoor <strong>air</strong> for each occupant<br />

● Included cartridge-type filters <strong>and</strong> upstream prefilters with a dust spot efficiency <strong>of</strong> 85 percent<br />

● Used controllable-pitch axial fans for supply <strong>and</strong> return <strong>air</strong><br />

● Included electric heaters for winter heating<br />

A microprocessor-base DDC system was used for zone temperature; AHU operating parameters;<br />

ice-charging, discharging, <strong>and</strong> direct cooling; <strong>and</strong> emergency smoke controls.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!