AC SYSTEMS: EVAPORATIVE COOLING 27.17<br />

The 55°F (12.8°C) all outdoor cooled <strong>air</strong> from the two-stage evaporative cooler provides cooling<br />

for 95 percent <strong>of</strong> the cooling hours. However, this cooled <strong>air</strong> temperature is again lowered to<br />

50°F (10.0°C) by the DX coil so that the space relative humidity in summer can be maintained at<br />

40 to 45 percent. This also reduces the supply volume flow as the <strong>air</strong> density is increased.<br />

Winter Heating. During winter heating, the heat-pipe heat exchanger uses exhaust heat to raise<br />

the outdoor <strong>air</strong> temperature from 0°F (�17.8°C) up to 42°F (5.6°C). As the supply volume flow<br />

rate is turned down 50 percent in winter, a DDC controller positions the outdoor <strong>and</strong> return themselves<br />

to introduce 76 percent outdoor <strong>air</strong> <strong>and</strong> 24 percent recirculating <strong>air</strong>. A 10 percent difference<br />

TABLE 27.2 System Characteristics <strong>of</strong> Indirect-Direct Two-Stage Evaporative Cooling Systems<br />

System structure<br />

Zone thermal <strong>and</strong> sound controls<br />

TSECS with or without DX <strong>refrigeration</strong><br />

Control zones Single zones or multiple zones<br />

Control method VAV or CV<br />

Control mode DDC, PI control mode, or on-<strong>of</strong>f<br />

Sound control<br />

Indoor <strong>air</strong> quality<br />

NC 30 to 45<br />

Minimum ventilation control All outdoor <strong>air</strong>, or 20% to 30% fixed amount <strong>of</strong> outdoor<br />

ventilation <strong>air</strong><br />

Filters<br />

Air systems<br />

Medium efficiency filters (MER 9 to 12)<br />

Types Two-stage evaporative VAV packaged system<br />

(VAV reheat)<br />

Supply fan, types Centrifugal, unhoused or plug fans<br />

Supply fan total pressure 3.0 to 4.0 in. WC<br />

Combined supply fan <strong>and</strong> motor drive efficiency 0.5<br />

Supply fan volume flow control Inlet vanes, variable-speed drives<br />

Return/relief fan Axial fan, centrifugal, unhoused or plug fans<br />

Return/relief fan total pressure<br />

Return fan volume flow control<br />

0.6 to 1.2 in. WC<br />

Supply-relief fan combination Automatically balanced<br />

Supply-return fan combination Space pressurization control<br />

Heat recovery Heat pipe heat exchanger, 0.65 effectiveness<br />

Operating modes<br />

Cooling systems<br />

Cooling, heating, nighttime setback, purging,<br />

warm-up, optimum start <strong>and</strong> stop<br />

Indirect evaporative cooler Effectiveness 0.6<br />

Direct evaporative cooler<br />

Refrigeration systems<br />

4- to 12-in. rigid media, saturation efficiency 90%<br />

Compressors Scroll, or reciprocating<br />

Energy use EER 10 to 12<br />

Capacity control Multiple units, staging on/<strong>of</strong>f<br />

Evaporator DX coil<br />

Condensers<br />

Heating systems<br />

Air-cooled or evaporatively-cooled<br />

Type Hot water reheat<br />

Boiler Gas <strong>and</strong> electric boilers<br />

Maintenance Sumps equipped with side-stream centrifugal slit<br />

separators; periodical flush <strong>of</strong> sumps