Selection <strong>and</strong> Installation<br />

REFRIGERATION SYSTEMS: COMPONENTS 10.33<br />

The evaporative condenser should be located as near to the compressor as possible. If it is located at<br />

a distance from the compressor, the discharge refrigerant pipe should be selected to have a pressure<br />

drop <strong>of</strong> 2°F (1.1°C) <strong>of</strong> saturated temperature difference <strong>of</strong> the refrigerant between the compressor<br />

<strong>and</strong> the condenser.<br />

If an evaporative condenser is located outdoors <strong>and</strong> will be operated during winter, its water<br />

basin <strong>and</strong> pump can be located indoors in a heated space. A water heater can be installed in the<br />

water basin, <strong>and</strong> the water should be drained back to the water basin as soon as the pump ceases to<br />

operate, to prevent freezing.<br />

To prevent the condensing pressure from falling below a certain value at which the expansion<br />

valve or other system components are difficult to operate, the capacity <strong>of</strong> the evaporative condenser<br />

is reduced by means <strong>of</strong> fan cycling, dampers, <strong>and</strong> fan speed modulation at low ambient temperatures,<br />

as in <strong>air</strong>-cooled condensers.<br />

The procedure for selecting <strong>and</strong> installing an evaporative condenser is as follows:<br />

1. Before selecting an evaporative condenser, calculate the total heat rejection <strong>of</strong> the refrigerating<br />

system Qrej, MBtu/h (kW).<br />

2. According to the refrigerant used in the system, select the appropriate material for the condenser<br />

coil. Copper tubes should be used for halocarbon refrigerants, <strong>and</strong> stainless steel or galvanized<br />

steel should be used for ammonia.<br />

3. Select a condenser coil that can provide a lower condensing temperature—below 95°F (35°C),<br />

if possible. This will save a lot <strong>of</strong> energy <strong>and</strong> reduce scale accumulation on the outer surface <strong>of</strong><br />

the condenser coil significantly compared with Tcon � 100 or 105°F (37.8 or 40.6°C).<br />

4. Based on the location <strong>of</strong> the evaporative condenser <strong>and</strong> the sound control requirement, it is <strong>of</strong>ten<br />

best to select a centrifugal fan. Check the volume flow rate <strong>and</strong> the fan total pressure that can be<br />

provided by the fan to overcome the pressure drop <strong>of</strong> the condenser coil <strong>and</strong> eliminator or <strong>air</strong><br />

duct, if any.<br />

5. Check the flow rate <strong>of</strong> the water spray <strong>of</strong> the circulating pump.<br />

6. For outdoor installation, select a casing <strong>and</strong> other system components that are weatherpro<strong>of</strong> <strong>and</strong><br />

corrosion-resistant.<br />

7. Install the evaporative condenser in a location where there is ample space for outdoor <strong>air</strong> intake<br />

<strong>and</strong> discharge. The influence <strong>of</strong> nearby exhaust systems should be avoided.<br />

Evaporative condensers have the advantage <strong>of</strong> lower condensing temperature <strong>and</strong> lower installation<br />

<strong>and</strong> energy costs. They are widely used in industrial applications <strong>and</strong> have been adopted more<br />

<strong>and</strong> more frequently in commercial buildings recently. The following reasons may explain why they<br />

were not previously popular in commercial <strong>and</strong> institutional applications:<br />

● Monthly maintenance, inspection, <strong>and</strong> cleaning are required to prevent buildup <strong>of</strong> scale on the<br />

condenser coil.<br />

● Water basin <strong>and</strong> water spraying system must be regularly inspected <strong>and</strong> cleaned to prevent the<br />

growth <strong>of</strong> Legionella bacteria <strong>and</strong> other microbiological growth. Water treatments with chemicals<br />

are <strong>of</strong>ten required. Mazurkiewicz (1996) reported that between the end <strong>of</strong> September <strong>and</strong> the beginning<br />

<strong>of</strong> October, 1996, there was a recent outbreak <strong>of</strong> Legionn<strong>air</strong>es’ disease in a food market’s<br />

evaporative condenser, in Farmington, Michigan.<br />

● Designers <strong>and</strong> operators have less experience with evaporative condensers.<br />

● Heat rejected from the evaporative condenser is more difficult to use in winter heating for energy<br />

conservation than that from a water-cooled condenser.