16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Part-Load Operation<br />

At cooling mode part-load operation as the zone sensible cooling load decreases, the zone temperature<br />

decreases accordingly. In a four-pipe fan-coil system, when the zone temperature sensor senses<br />

this temperature decrease, a DDC controller closes the two-way valve in a fan coil, reducing the<br />

chilled water flow rate entering the coil. As the chilled water flow reduces, the temperature <strong>of</strong><br />

chilled water leaving the fan coil Twfl rises accordingly, which raises both the temperature <strong>and</strong> humidity<br />

ratio <strong>of</strong> the conditioned (cooled <strong>and</strong> dehumidified) <strong>air</strong> leaving the fan coil Tfcp <strong>and</strong> wfcp as<br />

well as the humidity ratio <strong>of</strong> the zone <strong>air</strong> wrp, as shown in Fig. 28.1b. As soon as the reduction in<br />

the sensible cooling effect <strong>of</strong> the conditioned <strong>air</strong> due to the increase <strong>of</strong> Tfcp in Qs,fcp � 60V˙ fc�scpa<br />

(Tr � Tfcp) is just equal to the reduced sensible zone cooling load, a new balance is formed <strong>and</strong> the<br />

zone temperature is maintained at the indoor design temperture Tr. At cooling mode part-load operation, the chilled water temperature entering the fan coil <strong>and</strong> the<br />

cooling coil <strong>of</strong> the outdoor <strong>air</strong> AHU Twfe is better reset 5 to 7°F (2.8 to 3.9°C) higher, according to<br />

either the outdoor <strong>air</strong> temperature or the system load. Chilled water temperature reset can save compression<br />

energy <strong>and</strong> reduces the sensible cooling effect <strong>of</strong> the conditioned <strong>air</strong>. On the contrary, it<br />

also increases the zone relative humidty. Analyses should be done to select an appropriate value.<br />

During cooling mode part-load operation, reducing the chilled water flow rate entering a cooling<br />

coil to match the reduction in zone or space load always causes a higher zone relative humidty. But<br />

reducing the supply <strong>air</strong> volume flow rate to match the reduction in zone or space load in VAV systems<br />

causes the zone relative humidity to remain approximately the same.<br />

Zone Temperature Control <strong>and</strong> Sequence <strong>of</strong> Operations<br />

AIR CONDITIONING SYSTEMS: SPACE CONDITIONING SYSTEMS 28.13<br />

The zone temperature control <strong>of</strong> a four-pipe fan-coil system includes a fan-coil unit FC-1, using a<br />

separate cooling coil <strong>and</strong> a heating coil that serve a control zone rx1 in the perimeter zone, <strong>and</strong> the<br />

corresponding outdoor <strong>air</strong> AHU which supplies the conditioned outdoor ventilation <strong>air</strong> to the fan coil<br />

FC-1. The operating mode can be divided into cooling mode, deadb<strong>and</strong> mode, <strong>and</strong> heating mode.<br />

1. When the time-<strong>of</strong>-day clock signals the four-pipe fan-coil system in the <strong>of</strong>f position, <strong>and</strong> the<br />

outdoor <strong>air</strong> AHU <strong>and</strong> fan-coil unit serving control zone rx1 in the perimeter zone is shut <strong>of</strong>f, the<br />

two-way valves for both cooling <strong>and</strong> heating coils in the fan coil FC-1 should be closed. Also the<br />

outdoor <strong>air</strong> damper <strong>and</strong> the supply fan in the outdoor <strong>air</strong> AHU (OAAHU) are shut <strong>of</strong>f.<br />

2. When the time-<strong>of</strong>-day clock signals the four-pipe fan-coil system to the on position, <strong>and</strong> the<br />

perimeter zone temperature sensor senses a zone temperature T rx � 75°F (23.9°C), both the outdoor<br />

<strong>air</strong> AHU <strong>and</strong> fan coil FC-1 call for cooling. A DDC system controller then opens the two-way<br />

valves, resets the discharge <strong>air</strong> temperature T dis, <strong>and</strong> starts the supply fan motor <strong>of</strong> the OAAHU with<br />

the outdoor damper closed. After a time delay, such as 30 s, the outdoor damper <strong>of</strong> the OAAHU is<br />

fully opened.<br />

3. A DDC terminal controller next opens the two-way valve <strong>of</strong> the cooling coil <strong>of</strong> the fan coil,<br />

starts the fan motor <strong>and</strong> the small fan, <strong>and</strong> modulates the valve opening to maintain a zone temperature<br />

<strong>of</strong> 75°F (23.9°C). The two-way valve <strong>of</strong> the heating coil remains closed.<br />

4. During cooling mode part-load operation, the zone sensible cooling load reduces. When the<br />

drop in zone temperature T rx1p is sensed by the temperature sensor <strong>of</strong> control zone rx1, a DDC terminal<br />

controller reduces <strong>and</strong> modulates the opening <strong>of</strong> the two-way valve <strong>of</strong> the cooling coil in the<br />

fan coil, to maintain a preset zone temperature <strong>of</strong> 75°F (23.9°C).<br />

Because <strong>of</strong> the reduction in the chilled water flow in the cooling coil, the result is an increase in<br />

the temperature <strong>of</strong> chilled water leaving the cooling coil as well as in the temperature <strong>and</strong> humidity<br />

ratio <strong>of</strong> the cooled conditioned <strong>air</strong> leaving the coil, which results in a higher zone relative humidity<br />

� rp, as shown in Fig. 28.1b.<br />

Usually, the sensible heat ratio <strong>of</strong> the space <strong>conditioning</strong> line (SHR sp) at part load is smaller than<br />

that at summer design conditions. This further increases the zone relative humidity.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!