16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

21.42 CHAPTER TWENTY-ONE<br />

where Q rsxn � control zone maximum sensible cooling load, Btu/h (W). The control zone peak<br />

supply volume flow rate for cold <strong>air</strong> in the perimeter zone at summer design conditions is<br />

(21.13)<br />

For any control zone in the perimeter zone, the peak supply volume flow rate delivered to the<br />

conditioned space from the mixing VAV box, including 5 percent <strong>air</strong> leakage from the warm <strong>air</strong><br />

damper at summer design conditions, in cfm (L/s), is therefore<br />

V˙<br />

sxn � (21.14)<br />

Because only cold <strong>air</strong> from the VAV box is supplied to the interior zone, for any control zone in the interior<br />

zone, the peak supply volume flow rate V˙ sin at summer design conditions, in cfm (L/s), is then<br />

V˙<br />

sin � V˙<br />

rin<br />

(21.15)<br />

V˙ cxn<br />

0.95<br />

Peak supply volume flow rate for control zone n, , can be calculated by Eq. (21.12).<br />

Case Study: A Dual-Fan Dual-Duct VAV System<br />

Consider a dual-fan dual-duct VAV system serving a typical 20,000-ft 2 floor in an <strong>of</strong>fice building<br />

with the same operating parameters as the VAV reheat system described in Sec. 21.3, except the<br />

winter outdoor design temperature is 30°F (� 1.1°C) <strong>and</strong> the outdoor humidity ratio is 0.003 lb/lb<br />

(kg/kg). As in the VAV reheat system, the maximum supply volume flow rate for the interior zone<br />

at summer design conditions based on block load is<br />

For a control zone in the perimeter zone, if the temperature <strong>of</strong> the mixture <strong>of</strong> outdoor <strong>and</strong> recirculating<br />

<strong>air</strong> Tmx � 80.5°F (26.9°C), humidity ratio wmx � 0.010 lb/lb (kg/kg), Tsx � Ts,c � 55°F<br />

(12.8°C), <strong>and</strong> �sx � �s,c � 80 percent, draw line sx-mx as shown in Fig. 21.9b.<br />

For a warm <strong>air</strong> leakage <strong>of</strong> 0.05 from the inlet damper, the state point <strong>of</strong> the mixture <strong>of</strong> cold<br />

<strong>air</strong> supply <strong>and</strong> warm <strong>air</strong> leakage sxn can be determined. From the psychrometric chart, T sxn �<br />

56.5°F (13.6°C), <strong>and</strong> w sxn � 0.0083 lb/lb (kg/kg).<br />

The volume flow rate <strong>of</strong> cold <strong>air</strong> supply to the perimeter zone at summer design conditions, based<br />

on the block load <strong>and</strong> including 5 percent <strong>air</strong> leakage from the warm <strong>air</strong> inlet damper, is therefore<br />

The total cold <strong>air</strong> supply volume flow rate to both the perimeter zone <strong>and</strong> the interior zone at summer<br />

design conditions is<br />

(21.16)<br />

The volume flow rate <strong>of</strong> warm <strong>air</strong> supply in the perimeter zone is usually expressed as a percentage<br />

<strong>of</strong> peak supply volume flow rate <strong>of</strong> cold <strong>air</strong> in the perimeter zone, usually between 0.5V˙ scx <strong>and</strong><br />

1.0 . It depends mainly on the space heating load linear density qh,ft, in Btu/h�ft (W/m), <strong>and</strong> the<br />

V˙ scx<br />

V˙ si �<br />

V˙ scx �<br />

�<br />

Q rs<br />

60� sc pa(T r � T s,c)<br />

135,000<br />

60 � 0.075 � 0.243(75 � 55)<br />

V˙ sxn<br />

285,500<br />

60 � 0.075 � 0.243(75 � 56.5)<br />

V˙ s,c � V˙ scx � V˙ sci<br />

V˙ cxn � V˙ rxn � V˙ lk<br />

V˙ sin<br />

� 6173 cfm (2913 L / s)<br />

� 14,113 cfm (6660 L / s)<br />

� 14,113 � 6713 � 20,826 cfm (9828 L / s)<br />

V˙ sxn

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!