16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

21.48 CHAPTER TWENTY-ONE<br />

Fan-Powered VAV Boxes<br />

A fan-powered VAV box, or simply a fan-powered box, consists <strong>of</strong> a small forward-curved centrifugal<br />

fan, a VAV box, a heating coil (hot water or electric heater), a low-efficiency disposable filter,<br />

dampers, an outer casing, <strong>and</strong> corresponding controls, as shown in Fig. 21.14. Fan-powered VAV<br />

boxes can be classified as series <strong>and</strong> parallel boxes according to their construction <strong>and</strong> operating<br />

characteristics.<br />

Series Fan-Powered Box. In a series fan-powered box, a small centrifugal fan is connected in series<br />

with the cold primary <strong>air</strong>stream flowing through the VAV box, as shown in Fig. 21.14a. The<br />

volume flow <strong>of</strong> the cold primary <strong>air</strong> is varied at part-load operation, but after this <strong>air</strong> mixes with the<br />

induced plenum recirculating <strong>air</strong>, the fan delivers a continuously operated, nearly constant-volume<br />

flow rate <strong>of</strong> the mixture <strong>of</strong> cold primary <strong>air</strong> <strong>and</strong> plenum recirculating <strong>air</strong>. The mixture is then supplied<br />

to the control zones, either heated at the heating coil or without heating depending upon the<br />

zone load.<br />

Because the <strong>air</strong>flow from the series fan-powered box is constant, it is easier to select ceiling diffusers<br />

to achieve good space <strong>air</strong> diffusion. In a series fan-powered box, cold primary <strong>air</strong> is thoroughly<br />

mixed with plenum recirculating <strong>air</strong>. The main disadvantage <strong>of</strong> a series fan-powered box is<br />

its larger fan, which consumes more energy than a parallel fan-powered box.<br />

Parallel Fan-Powered Box. In a parallel fan-powered box, the induced recirculating plenum<br />

<strong>air</strong>stream discharged from the centrifugal fan is connected in parallel with the cold primary<br />

<strong>air</strong>stream discharged from the VAV box in the fan-powered box. These two <strong>air</strong>streams are mixed either<br />

before or after the heating coil <strong>and</strong> then are supplied to the control zones.<br />

A parallel fan-powered box with a heating coil located upstream from the fan is called a drawthrough<br />

parallel fan-powered box, as shown in Fig. 21.14b. When the heating coil is located downstream<br />

from the fan, the box is called a blow-through parallel fan-powered box, shown in<br />

Fig. 21.14c. The <strong>air</strong> temperature entering the heating coil <strong>of</strong> a draw-through unit is the temperature<br />

<strong>of</strong> recirculating plenum <strong>air</strong>, which is higher than that <strong>of</strong> the mixture <strong>of</strong> cold primary <strong>air</strong> <strong>and</strong> recirculating<br />

plenum <strong>air</strong> in a blow-through box.<br />

A parallel fan-powered box operates only when there is a need to mix the warm plenum <strong>air</strong> with<br />

the cold primary <strong>air</strong> at summer cooling mode part-load operation, when the volume flow <strong>of</strong> the cold<br />

primary <strong>air</strong> is at its minimum setting or other preset value, or when the mixture <strong>of</strong> cold primary <strong>air</strong><br />

<strong>and</strong> warm plenum <strong>air</strong> is heated at the heating coil to <strong>of</strong>fset the zone winter heating load. When a<br />

parallel fan-powered box is used to mix 40 to 50°F (4.4 to 10.0°C) low-temperature primary <strong>air</strong><br />

with warm plenum <strong>air</strong> in a cold <strong>air</strong> distribution system, it is also operated continuously during summer<br />

cooling mode.<br />

In a parallel fan-powered box when the cold primary <strong>air</strong>stream is reduced to its minimum setting<br />

during cooling mode part-load operation, the volume flow rate <strong>of</strong> the extracted plenum recirculating<br />

<strong>air</strong> plus the cold primary <strong>air</strong> is usually equal to 0.80 to 1.0 <strong>of</strong> the zone summer peak supply volume<br />

flow rate . The fan in a parallel fan-powered box extracts only recirculating plenum <strong>air</strong>, <strong>and</strong><br />

V˙ sn,d<br />

therefore it has a smaller volume flow rate <strong>and</strong> a lower fan total pressure than that in a series fanpowered<br />

box. Because <strong>of</strong> its smaller fan size, it consumes less fan power in cooling mode<br />

operation.<br />

Current parallel fan-powered box designs also provide a good mixture <strong>of</strong> cold primary <strong>air</strong> <strong>and</strong><br />

extracted plenum <strong>air</strong>. Some <strong>of</strong> the recent models use a variable-speed small parallel fan. It energizes<br />

as soon as the supply volume flow <strong>of</strong> the cold primary <strong>air</strong> drops at cooling mode part-load operation.<br />

The extracted recirculating plenum <strong>air</strong> gradually increases as the volume flow <strong>of</strong> cold primary<br />

<strong>air</strong> decreases up to a maximum limit between 0.4 <strong>and</strong> 0.5 . Under this condition, the zone<br />

supply volume flow rate is kept nearly constant. Parallel fan-powered boxes are <strong>of</strong>ten used in cold<br />

<strong>air</strong> distribution because <strong>of</strong> their lower initial cost <strong>and</strong> lower fan energy consumption.<br />

In a parallel fan-powered box, a backdraft damper should be installed upstream from the fan.<br />

This damper is normally closed to prevent the backward flow <strong>of</strong> cold primary <strong>air</strong> in case the fan is<br />

deenergized. When the fan is turned on, the backdraft damper is fully opened.<br />

V˙ sn,d<br />

V˙ sn,d

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!