6.48 CHAPTER SIX<br />

Area <strong>of</strong> perimeter zone<br />

Area <strong>of</strong> interior zone<br />

Floor-to-floor height<br />

Floor-to-ceiling height<br />

Window:<br />

Percentage <strong>of</strong> glass/exterior wall<br />

U value<br />

Interior shading, SC<br />

Exterior wall:<br />

Length<br />

Height<br />

U value<br />

Partition wall:<br />

Length<br />

Height<br />

U value<br />

6300 ft 2 (586 m 2 )<br />

5600 ft 2 (520 m 2 )<br />

13 ft (4 m)<br />

9 ft (2.74 m)<br />

This typical floor has the following internal loads: The occupant density is 7 persons per 1000<br />

ft 2 (93 m 2 ). For each person, there is 250 Btu/h (73 W) sensible heat gain, <strong>and</strong> 250 Btu/h (73 W)<br />

latent heat gain. The lighting load, including ballast allowance, is 1 W/ft 2 (10.7 W/m 2 ). The miscellaneous<br />

equipment load due to personal computers <strong>and</strong> appliances is 1 W/ft 2 (10.7 W/m 2 ).<br />

FIGURE 6.9 Typical plan <strong>of</strong> a high-rise <strong>of</strong>fice building.<br />

0.345<br />

0.67 Btu/h�ft 2 �°F (3.8 W/m 2 �°C)<br />

0.36<br />

120 ft (36.6 m)<br />

13 ft (2.74 m)<br />

0.12 Btu/ h�ft 2 �°F (0.68 W/(m 2 �°C)<br />

200 ft (61 m)<br />

9 ft (2.74 m)<br />

0.12 Btu/h�ft 2 �°F (0.68 W/m 2 �°C)