16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

ASHRAE St<strong>and</strong>ard 62-1999<br />

control, a volume flow <strong>of</strong> outdoor <strong>air</strong> that exceeds the amount <strong>of</strong> minimum outdoor ventilation <strong>air</strong> is<br />

always supplied to the conditioned space. Ventilation problems <strong>of</strong>ten occur during minimum outdoor<br />

<strong>air</strong> recirculating mode, i.e., minimum ventilation controls. Currently used minimum ventilation<br />

controls in VAV systems include the following:<br />

CO 2-based dem<strong>and</strong>-controlled ventilation<br />

Mixed plenum pressure controls<br />

Outdoor <strong>air</strong> injection fan control<br />

Fan tracking control<br />

AIR SYSTEMS: MINIMUM VENTILATION AND VAV SYSTEM CONTROLS 23.3<br />

As discussed in Sec. 4.10, ASHRAE St<strong>and</strong>ard 62-1999, Ventilation for Acceptable Indoor Air Quality,<br />

specifies two alternative procedures to obtain acceptable IAQ:<br />

1. Ventilation rate procedure. In the ventilation rate procedure, acceptable indoor <strong>air</strong> quality is<br />

achieved by providing ventilation <strong>air</strong> <strong>of</strong> specified quality <strong>and</strong> quantity to the conditioned space.<br />

This procedure prescribes the following:<br />

● The quality <strong>of</strong> the outdoor <strong>air</strong> shall be acceptable for ventilation, i.e., contaminants in outdoor <strong>air</strong><br />

do not exceed the concentrations listed in the Table <strong>of</strong> National Primary Ambient-Air Quality<br />

St<strong>and</strong>ards by EPA in Sec. 4.10.<br />

● Outdoor <strong>air</strong> treatments are required when necessary.<br />

● Ventilation rates for typical spaces are listed in Table 4.5. For details, refer to ASHRAE St<strong>and</strong>ard<br />

62-1999.<br />

● Ventilation systems for spaces with intermittent or variable occupancy may have their outdoor <strong>air</strong><br />

quantity adjusted by damper or cycling <strong>of</strong> fan operation to provide sufficient dilution to maintain<br />

contaminant concentrations within acceptable levels at all times.<br />

● For intermittent occupancy, when contaminants are associated only with occupants or occupant<br />

activities, do not result a health hazard because contaminants are dissipated during unoccupied<br />

periods.<br />

● When contaminants are independent <strong>of</strong> occupants or occupant acivities, the supply <strong>of</strong> outdoor <strong>air</strong><br />

should lead occupancy lag or lead time depending on the ventilation rate <strong>and</strong> <strong>air</strong> capacity per person<br />

in the space.<br />

● Where peak occupancies are less than 3 h in duration, the outdoor <strong>air</strong>flow rate may be determined<br />

according to average occupancy for the duration <strong>of</strong> operation <strong>of</strong> the system provided the average<br />

occupancy used is not less than half <strong>of</strong> the maximum.<br />

2. Indoor <strong>air</strong> quality procedure. In the indoor <strong>air</strong> quality procedure, acceptable <strong>air</strong> quality is<br />

achieved within the conditioned space by restricting the concentration <strong>of</strong> all known contaminants <strong>of</strong><br />

concern to some specified acceptable levels. The acceptable concentration level in Table <strong>of</strong> National<br />

Primary Ambient-Air Quality St<strong>and</strong>ards, as listed in Sec. 4.10, also applies indoors for the same exposure<br />

time. The following limits apply for four other indoor contaminants according to St<strong>and</strong>ard<br />

62-1999:<br />

Contaminant Concentration ppm Exposure time<br />

Carbon dioxide CO2 1.8 g/m 3 1000 Continuous<br />

Chlordane 5 �g/m3 0.0003 Continuous<br />

Ozone 100 �g/m3 0.05 Continuous<br />

Radon 4 pCi/L Annual average

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!