16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

7.56 CHAPTER SEVEN<br />

loops. However, the pressure characteristics <strong>of</strong> the supply <strong>and</strong> return mains <strong>of</strong> the distribution loop at<br />

reduced flows make it difficult to satisfy various load pr<strong>of</strong>iles in different buildings during part-load<br />

operation. Having a variable-speed building pump for each building also saves more pump energy.<br />

Therefore, the use <strong>of</strong> variable-speed pumps for both distribution <strong>and</strong> building loops is preferable.<br />

Control <strong>of</strong> Variable-Speed Distribution Pump. Two types <strong>of</strong> controls can be used to modulate a<br />

variable-speed distribution pump to transport the required chilled water volume flow to various<br />

buildings:<br />

● A differential-pressure transmitter may be located near the farthest end <strong>of</strong> the distribution supply<br />

main, as shown in Fig. 7.22a. Theoretically, the head <strong>of</strong> the building pump should extract the exact<br />

required amount <strong>of</strong> chilled water corresponding to the sum <strong>of</strong> the coil loads in the building<br />

loop, force it through the coils, <strong>and</strong> discharge it to the distribution return main. Therefore, a set<br />

point for the pressure differential <strong>of</strong> about 5 ft (1.5 m) may be appropriate. This type <strong>of</strong> control is<br />

widely used.<br />

● A DDC system measures the total water flow that returns from each building by means <strong>of</strong><br />

flowmeters <strong>and</strong> modulates the variable-speed distribution pump to supply exactly the required<br />

amount to various building loops. This type <strong>of</strong> control is more precise but more expensive.<br />

Building Entrance. Chilled water is usually supplied directly from the distribution supply main<br />

to the building supply main. A pressure throttling valve may be used to <strong>of</strong>fset the excess pressure<br />

differential �H s,r along the distribution loop.<br />

Although using a heat exchanger at the building entrance entirely isolates the chilled water in<br />

the distribution loop from the chilled water in the building loop, a temperature increase <strong>of</strong> about 3<br />

to 7°F (1.7 to 3.9°C) is required for a chilled water heat exchanger. Because chilled water has a supply<br />

<strong>and</strong> return temperature differential <strong>of</strong> only about 15 to 20°F (8.3 to 11.1°C), a heat exchanger is<br />

seldom used at a building or zone entrance for a chilled water system. Because a hot water system<br />

has a greater supply <strong>and</strong> return temperature differential, a heat exchanger is sometimes used at the<br />

building entrance for a hot water system.<br />

A chilled water building loop may be divided into various zones based on different height levels<br />

within the building. In such an arrangement, the coils in the lower floors <strong>of</strong> the building loop will<br />

not suffer a high static pressure because the low-level water loop is <strong>of</strong>ten isolated from the highlevel<br />

water loop by means <strong>of</strong> a heat exchanger at the zone entrance.<br />

If a building requires a chilled water supply temperature higher than that given by the distribution<br />

supply main, a crossover bridge with a temperature control valve can be arranged for this purpose,<br />

as shown in Fig. 7.22c.<br />

The return temperature from the coils in a building loop is affected by the cleanliness <strong>of</strong> the coil,<br />

including <strong>air</strong>-side cleanliness, <strong>and</strong> the control system in the building loop. The building’s variablespeed<br />

pump is <strong>of</strong>ten controlled by the pressure-differential transmitter located at the end <strong>of</strong> the<br />

building supply main, as shown in Fig. 7.22a <strong>and</strong> c.<br />

Plant-Distributed Building Loop<br />

A plant-distributed building loop water system has nearly the same configuration as a plant-distribution-building<br />

loop system except that there is no distribution pump in the distribution loop. Constant-speed<br />

chiller/boiler pumps in the plant loop supply water to the beginning <strong>of</strong> the supply main<br />

<strong>of</strong> the distribution loop, point S, <strong>and</strong> extract water from the end <strong>of</strong> the return main <strong>of</strong> the distribution<br />

loop, point R. Various variable-speed building pumps in the building loops extract water from<br />

the distribution main point S. They also overcome the pressure loss <strong>of</strong> the distribution supply main<br />

piping up to the building entrance, the pressure loss <strong>of</strong> the building loop �p bg including building<br />

supply <strong>and</strong> return mains, coils, two-way control valve, <strong>and</strong> fittings; <strong>and</strong> the pressure loss <strong>of</strong> the distribution<br />

return main piping from the building outlet to point R.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!