16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

5.66 CHAPTER FIVE<br />

5.16 CONTROLS IN ASHRAE/IESNA STANDARD 90.1-1999<br />

General<br />

Off-Hour Controls<br />

ASHRAE/IESNA St<strong>and</strong>ard 90.1-1999, Energy St<strong>and</strong>ard for Buildings Except Low-Rise Residential<br />

Buildings, specifies the following m<strong>and</strong>atory provisions for HVAC&R controls. For exceptions <strong>and</strong><br />

details refer to St<strong>and</strong>ard 90.1-1999.<br />

● Thermostatic controls. The supply <strong>of</strong> heating <strong>and</strong> cooling energy to each zone shall be controlled<br />

individually by thermostatic controls using the zone temperature as the response. A dwelling unit<br />

is permitted to be considered as a single zone.<br />

● Dead b<strong>and</strong>. When both heating <strong>and</strong> cooling are controlled, zone thermostatic controls shall be capable<br />

<strong>of</strong> providing a temperature range or dead b<strong>and</strong> <strong>of</strong> at least 5°F (2.8°C). Within that range the<br />

heating <strong>and</strong> cooling energy supplied to the zone is shut <strong>of</strong>f.<br />

● Set-point overlap. When heating <strong>and</strong> cooling supply to a zone are controlled by separate zone<br />

thermostatic controls, means such as limit switches, mechanical stops, <strong>and</strong> s<strong>of</strong>tware for DDC systems,<br />

shall be provided to prevent the heating set point exceeding the cooling set point minus any<br />

proportional b<strong>and</strong>.<br />

HVAC systems with a design heating or cooling capacity greater than 65,000 Btu/h (19,050 W) <strong>and</strong><br />

3 fan system power greater than �4 hp (0.56 kW) shall have all the following <strong>of</strong>f-hour controls: automatic<br />

shutdown, setback controls, optimum start controls, shut<strong>of</strong>f damper controls, <strong>and</strong> zone isolation.<br />

● Automatic shutdown. HVAC systems shall be equipped with at least one <strong>of</strong> the following:<br />

1. Controls that can start <strong>and</strong> stop the system under different time schedules, are capable <strong>of</strong> retaining<br />

programming <strong>and</strong> time setting during loss <strong>of</strong> power for a period at least 10 hours, <strong>and</strong><br />

include an accessible manual override or equivalent that allows temporary operation <strong>of</strong> the<br />

system for up to 2 hours.<br />

2. An occupancy sensor that can shut the system <strong>of</strong>f when no occupant is sensed for a period <strong>of</strong><br />

up to 30 minutes.<br />

3. A manual operated timer that can adjust the system for two hours.<br />

4. An interlock to a security system which shuts the system <strong>of</strong>f when the security system is<br />

activated.<br />

● Setback controls. A heating system located where the heating outdoor design temperature is 40°F<br />

(4.4°C) or less shall be equipped with controls that can automatically restart <strong>and</strong> temporarily operate<br />

the system as required to maintain zone temperature above a heating set point adjustable<br />

down to 55°F (12.8°C) or lower. A cooling system located where the cooling outdoor design temperature<br />

is greater than 100°F (37.8°C) shall be equipped with controls that can automatically<br />

restart <strong>and</strong> temporarily operate the system as required to maintain zone temperature below a cooling<br />

set point adjustable up to 90°F (32.2°C) or higher or to prevent high space humidity.<br />

● Optimum start controls. An <strong>air</strong> system with a supply volume flow rate exceeding 10,000 cfm<br />

(4720 L/s), served by one or more supply fans, shall have optimum controls. The optimum start<br />

shall be at least a function <strong>of</strong> the difference between space temperature <strong>and</strong> occupied setpoint, <strong>and</strong><br />

the amount <strong>of</strong> time prior to scheduled occupancy.<br />

● Shut<strong>of</strong>f damper controls. Both outdoor <strong>air</strong> supply <strong>and</strong> exhaust system shall be installed with motorized<br />

dampers that will automatically shut <strong>of</strong>f when the systems or the space are not in use. Out-

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!