16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Thermal Stratification<br />

divided into two groups: highly energy-efficient Model Conservation St<strong>and</strong>ard (MCS) houses <strong>and</strong> a<br />

control group built to current (regional) practice (CP) or st<strong>and</strong>ards. Ducted heating systems in CP<br />

houses had 26 percent more <strong>air</strong> leakage than unducted systems <strong>and</strong> used 40 percent more heating<br />

energy. Ducted heating systems in MCS houses had 22 percent more <strong>air</strong> leakage <strong>and</strong> used 13 percent<br />

more heating energy than unducted MCS houses.<br />

Gammage et al. (1986) studied the ducted warm <strong>air</strong> systems <strong>of</strong> 31 Tennessee houses. They<br />

found that the <strong>air</strong> infiltration rate was 0.44 ach when the forced-<strong>air</strong> systems were <strong>of</strong>f <strong>and</strong> 0.78 ach<br />

when the forced-<strong>air</strong> systems were on.<br />

Field tests have also shown that leakages are greater for the return duct than for the supply<br />

duct because <strong>of</strong> the greater importance <strong>of</strong> the supply <strong>air</strong>. Also, the return plenum is <strong>of</strong>ten not<br />

carefully sealed. In five Florida homes with low-pressure ducted warm <strong>air</strong> systems with supply<br />

<strong>and</strong> return plenums, Cummings <strong>and</strong> Tooley (1989) found that when rep<strong>air</strong>s were made to seal<br />

the return plenums, the infiltration in these five homes dropped from an average <strong>of</strong> 1.42 ach to<br />

0.31 ach.<br />

When a ducted warm <strong>air</strong> heating system is operating, supply duct leakage in such nonconditioned<br />

space as the attic or basement raises the space pressure to a positive value <strong>and</strong> promotes<br />

exfiltration. Return duct leakage extracts the space <strong>air</strong>, lowers the space pressure to a negative<br />

value, <strong>and</strong> promotes infiltration. Both types <strong>of</strong> leakage increase the whole-house infiltration.<br />

Suggested remedies to reduce duct leakage <strong>and</strong> energy use are as follows:<br />

● Externally seal the duct with tape; seal the ducts internally if possible.<br />

● Seal the return plenum <strong>and</strong> equipment if there is leakage. Seal the duct, pipes, <strong>and</strong> cable penetrations<br />

through the structures.<br />

● Avoid locating ducts in unconditioned spaces. Provide insulation for ducts running in unconditioned<br />

spaces.<br />

● For a low-pressure ducted warm <strong>air</strong> system without return ducts, an adequate door undercut or<br />

door louver should be provided.<br />

A low-pressure ducted warm <strong>air</strong> heating system with a gas-fired furnace always has a high supply<br />

temperature differential �T s. If �T s exceeds 30°F (16.7°C), or if there is a high ceiling, thermal<br />

stratification may form in the conditioned space. The vertical temperature difference may be greater<br />

than 5°F (2.8°C) <strong>and</strong> cause discomfort, as mentioned in Sec. 4.8. In addition, a higher temperature<br />

near the ceiling may increase heat transfer through the ceiling, attic, <strong>and</strong> ro<strong>of</strong>.<br />

A greater supply <strong>air</strong> volume flow rate, lower �T s, higher downward <strong>air</strong> jet velocity, <strong>and</strong> suitable<br />

location for the supply grille are remedial measures that reduce thermal stratification <strong>and</strong> vertical<br />

temperature differences.<br />

Part-Load Operation <strong>and</strong> Control<br />

HEATING SYSTEMS, FURNACES, AND BOILERS 8.21<br />

For low-pressure ducted warm <strong>air</strong> heating systems, a thermostat or a temperature sensor is usually<br />

installed in a representative space to control the gas valve <strong>of</strong> a furnace operating under an on/<strong>of</strong>f or<br />

two-stage step control mode to maintain the required space temperature. The proportion <strong>of</strong> on <strong>and</strong><br />

<strong>of</strong>f time in each operating on/<strong>of</strong>f cycle varies to meet the varying space heating load. Figure 8.6<br />

shows a typical on/<strong>of</strong>f control for a gas furnace, resulting in a temperature variation for a point<br />

20 ft (6.1 m) downstream <strong>of</strong> the supply plenum <strong>and</strong> at the supply register.<br />

When the space temperature increases above the upper limit as the space heating load falls, the<br />

controller shuts <strong>of</strong>f the gas valve so that the heat supply to the space is cut <strong>of</strong>f. When the space temperature<br />

falls below the lower limit, the gas valve will open again <strong>and</strong> raise the space temperature.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!