16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

6.46 CHAPTER SIX<br />

● For the calculation <strong>of</strong> the energy use, only when the outdoor ventilation <strong>air</strong> system is separated<br />

from the main supply system is it then possible to choose <strong>and</strong> to create a schedule in<br />

which the <strong>air</strong>flow <strong>of</strong> outdoor ventilation <strong>air</strong> varies according to people’s occupancy.<br />

● During the calculation <strong>of</strong> energy use for a variable-<strong>air</strong>-volume (VAV) system, the <strong>air</strong>flow <strong>of</strong><br />

the outdoor ventilation <strong>air</strong> may be varied based on its control systems into the following<br />

schedule: 100 percent, 24 h/day; varying according to supply volume flow <strong>of</strong> the <strong>air</strong> system;<br />

varying according to people’s occupancy.<br />

● For the calculation <strong>of</strong> energy use due to infiltration, choose <strong>and</strong> create a schedule in which<br />

the infiltration varies inversely with supply fan schedule, such as for hours fan schedule<br />

is 100 percent, infiltration is zero; then when fan schedule is 0 percent, the infiltration is<br />

100 percent.<br />

3. Operating schedules <strong>of</strong> fans that affect the design load <strong>and</strong> energy use calculations are as<br />

follows:<br />

● At design load, TRACE 600 assumes that the main supply fan <strong>and</strong> auxiliary fan, if any, are<br />

scheduled at 100 percent, 24 h/day as the default value during cooling mode operation, <strong>and</strong><br />

fan heat will be included in the cooling coil load. Similarly, at design load, main supply <strong>and</strong><br />

auxiliary fans are scheduled at 0 percent, 24 h/day during heating mode operation, <strong>and</strong> no<br />

fan heat will be taken into account.<br />

● In the energy use calculation, main supply <strong>and</strong> auxiliary fans in a constant-volume <strong>air</strong> system<br />

are scheduled at 100 percent, 24 h/day. Or choose or create a schedule at which fans will be<br />

cycling (on <strong>and</strong> <strong>of</strong>f) depending on the space cooling <strong>and</strong> heating load.<br />

● In the energy use calculation, main supply <strong>and</strong> auxiliary fans in a VAV system are scheduled<br />

depending on the space cooling <strong>and</strong> heating load.<br />

● For a room exhaust fan operated at cooling design load, it is scheduled at 100 percent,<br />

24 h/day as the default value. For the energy use calculation, choose or create an appropriate<br />

operating schedule.<br />

4. The reheat minimum percentage determines the ratio <strong>of</strong> reheat minimum <strong>air</strong>flow for that room<br />

to the design supply <strong>air</strong>flow.<br />

5. Daylighting schedule describes the availability <strong>of</strong> daylighting each hour. Choose an available<br />

schedule or create an appropriate daylighting schedule.<br />

Trace 600 Input—Internal Loads<br />

Four cards cover the input data <strong>of</strong> internal loads <strong>and</strong> <strong>air</strong>flows.<br />

Card 27, people <strong>and</strong> lights, describes the room number, people’s density <strong>and</strong> corresponding unit,<br />

people’s sensible <strong>and</strong> latent loads, lighting heat gain <strong>and</strong> corresponding unit, type <strong>of</strong> lighting<br />

fixture, ballast factor, <strong>and</strong> daylighting reference points 1 <strong>and</strong> 2, to show whether there is<br />

daylighting control or one or two control areas. According to the types <strong>of</strong> lighting fixtures <strong>and</strong><br />

the return <strong>air</strong>flow per unit floor area, the percentage <strong>of</strong> lighting load to return <strong>air</strong> should be<br />

determined more precisely. Refer to Sec. 6.6 for details.<br />

Card 28, miscellaneous equipment (optional), covers the room number, miscellaneous equipment<br />

reference number, equipment description, energy consumption value <strong>and</strong> corresponding<br />

units, schedule <strong>and</strong> energy metering code, percentage <strong>of</strong> sensible load, percentage <strong>of</strong> miscellaneous<br />

equipment load to space <strong>and</strong> to <strong>air</strong> path, radiant fraction, <strong>and</strong> whether the plenum <strong>air</strong>,<br />

exhaust <strong>air</strong>, or return <strong>air</strong> path picks up the miscellaneous load.<br />

Card 29, room <strong>air</strong>flows, covers the flow rates <strong>of</strong> outdoor ventilation <strong>air</strong> during cooling <strong>and</strong> heating<br />

operation <strong>and</strong> their corresponding units, the flow rates <strong>of</strong> infiltration <strong>air</strong> for cooling <strong>and</strong><br />

heating <strong>and</strong> their corresponding units, <strong>and</strong> the amount <strong>of</strong> minimum reheat <strong>and</strong> its units.<br />

Card 30, fan flow rates, describes the room number, <strong>air</strong>flow <strong>of</strong> the main <strong>and</strong> auxiliary cooling <strong>and</strong><br />

heating supply fans <strong>and</strong> their corresponding units, <strong>and</strong> <strong>air</strong>flow <strong>of</strong> room exhaust fan <strong>and</strong> its unit.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!