16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

13.12 CHAPTER THIRTEEN<br />

System Characteristics<br />

P6 or st<strong>and</strong>by pump P7 <strong>and</strong> to the interior zone through zone pump P4 or st<strong>and</strong>by pump P5. The<br />

chilled water supply temperature T ws is usually between 42 <strong>and</strong> 45°F (5.6 <strong>and</strong> 7.2°C). Chilled water<br />

pump P1 <strong>and</strong> hot water pump P2 are both constant-speed, constant-flow pumps. Zone pumps P5,<br />

P6, P7, <strong>and</strong> P8 are all variable-speed, variable-flow pumps.<br />

Unoccupied Cooling Mode. When T r, p � 75°F (23.9°C) <strong>and</strong> the space is unoccupied, as<br />

determined by a timer, the DDC unit controller shuts down the entire centrifugal chiller <strong>and</strong> heat<br />

recovery system.<br />

Occupied Heating Mode. When T r, p � 70°F (21.1°C) <strong>and</strong> the conditioned space is occupied, the<br />

system is under occupied heating mode operation. The centrifugal chiller is energized, <strong>and</strong> pump<br />

P1 supplies chilled water to the interior zone through zone pumps P4 <strong>and</strong> P5. At the same time, the<br />

DDC unit controller actuates the two-position valve V2 to block passage <strong>of</strong> chilled water to<br />

the perimeter zone. Hot water pump P2 is energized so that hot water from the heating bundle in<br />

the condenser is forced through the deenergized supplementary heater <strong>and</strong> supplied to heating coils<br />

in the perimeter zone through zone pump P6 or P7 at a temperature T sup between 105 <strong>and</strong> 110°F<br />

(40.6 <strong>and</strong> 43.3°C). If the rejected heat in the heating bundle is more than that required in the heating<br />

coils in the perimeter zone, the return water temperature T ret increases before the inlet <strong>of</strong> the<br />

heating bundle <strong>and</strong> pump P2. When sensor T2 detects such a rise in temperature, the DDC unit<br />

controller modulates valve V1, which permits some hot water to flow to the storage tank. When<br />

the storage tank is full <strong>of</strong> hot water <strong>and</strong> sensor T2 detects a further increase in water temperature,<br />

the modulation valve is positioned so as to allow all the hot water to bypass the storage tank. Tower<br />

pump P3 starts, <strong>and</strong> valve V3 is modulated to control the flow rate <strong>of</strong> condenser water to the<br />

cooling tower.<br />

If the outdoor temperature T o is so low that heat rejection at the heating bundle is not sufficient<br />

to meet the heating requirement at the perimeter zone, then the hot water temperature detected by<br />

sensor T2 is less than a preset value. The tower pump is then stopped. Hot water bypasses the storage<br />

tank, <strong>and</strong> the supplementary heater is gradually energized so as to maintain the water temperature<br />

sensed by T2 within a predetermined range.<br />

Unoccupied Heating Mode. When T o � 70°F (21.1°C) <strong>and</strong> the conditioned space is unoccupied,<br />

the DDC unit controller comm<strong>and</strong>s the following actions:<br />

1. The hot water temperature detected by sensor T2 is reset to a value according to outdoor temperature<br />

T o to maintain a night setback indoor temperature T r � 55°F (12.8°C) <strong>and</strong> lower.<br />

2. Only hot water pump P2 <strong>and</strong> zone pump P6 or P7 are in operation; all other equipment ceases to<br />

operate.<br />

3. Valve V1 is modulated so that hot water from the storage tank alone is supplied to the heating<br />

coils in the perimeter zone.<br />

If T2 senses a water temperature lower than the preset value, the supplementary heater is then gradually<br />

energized. The modulating valve V1 allows the hot water to bypass the storage tank <strong>and</strong> then<br />

enter the heaters.<br />

First, compared with a cooling-only centrifugal chiller, the <strong>refrigeration</strong> cycle <strong>of</strong> a centrifugal<br />

chiller incorporating a heat recovery system has a greater pressure differential between condensing<br />

<strong>and</strong> evaporating pressure �p e,c, in psi (kPa). This is because a cooling-only chiller usually has<br />

water leaving the condenser at a temperature at 90 to 95°F (32.2 to 35°C) during summer design<br />

conditions, whereas a chiller incorporating heat recovery needs a higher condenser leaving temperature<br />

T cl <strong>of</strong> 105 to 110°F (40.6 to 43.3°C) for the hot water supply in winter heating. Although the<br />

evaporating temperature can be slightly higher in winter than in summer, an increase <strong>of</strong> 10 to 12°F

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!