variable-flow water system installed with a constant-speed pump, the design system operating<br />

point is preferably located to the left <strong>of</strong> the region <strong>of</strong> pump maximum efficiency, because the system<br />

operating point <strong>of</strong> an oversized pump moves into or nearer to the region <strong>of</strong> pump maximum<br />

efficiency.<br />

Combination <strong>of</strong> Pump-Piping Systems<br />

When two pump-piping systems 1 <strong>and</strong> 2 are connected in series as shown in Fig. 7.15a, the volume<br />

flow rate <strong>of</strong> the combined pump-piping system, [gpm (m3 /s)] is<br />

V˙ 1<br />

V˙ 2<br />

FIGURE 7.14 Water system curve <strong>and</strong> system operating point.<br />

V˙ com<br />

V˙ com � V˙ 1 � V˙ 2<br />

(7.12)<br />

where <strong>and</strong> are the volume flow rate <strong>of</strong> pump-piping systems 1 <strong>and</strong> 2, gpm (m3 /s). The total<br />

head lift <strong>of</strong> the combined system �Hcom [ft WC (m WC)] is<br />

�H com ��H 1 ��H 2<br />

(7.13)<br />

where �H1 <strong>and</strong> �H2 are the head <strong>of</strong> pump-piping systems 1 <strong>and</strong> 2, ft WC (m WC).<br />

It is simpler to use one system curve to represent the whole system, i.e., to use a combined system<br />

curve. The system operating point <strong>of</strong> the combined pump-piping system is illustrated by point<br />

P with a volume flow <strong>of</strong> V˙ P <strong>and</strong> head <strong>of</strong> �HP. The purpose <strong>of</strong> connecting pump-piping systems in<br />

series is to increase the system head.<br />

When a pump-piping system has parallel-connected water pumps, its volume flow rate V˙ [gpm<br />

(m 3 /s)] is the sum <strong>of</strong> the volume flow rates <strong>of</strong> the constituent pumps , , etc. The head <strong>of</strong> each<br />

constituent pump <strong>and</strong> the head <strong>of</strong> the combined pump-piping system are equal. It is more convenient<br />

to draw a combined pump curve <strong>and</strong> one system curve to determine their intersection, the<br />

system operating point P, as shown in Fig. 7.15b. The purpose <strong>of</strong> equipping a water system with<br />

parallel-connected water pumps is to increase its volume flow rate.<br />

V˙ 1<br />

V˙ 2<br />

WATER SYSTEMS 7.35