16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Steam Humidifier Control<br />

Dew Point Control<br />

AIR SYSTEMS: MINIMUM VENTILATION AND VAV SYSTEM CONTROLS 23.27<br />

spaces that have been unoccupied less than or greater than 24 h <strong>and</strong> provide an optimum start or<br />

stop time <strong>of</strong> the <strong>air</strong> system.<br />

A simple <strong>and</strong> effective way that is worthwhile to try is as follows: Record the outdoor <strong>air</strong> temperature,<br />

space temperature, relative humidity, internal load, <strong>and</strong> equipment <strong>and</strong> damper operating<br />

conditions at suitable time intervals, say, 10 min to 1 h, during the warm-up or cool-down period;<br />

analyze <strong>and</strong> determine the optimum start time once sufficient data have been accumulated. Modify<br />

the results until they are verified by experience.<br />

Some manufacturers also provide cycling capacity during morning warm-up to maintain the<br />

space temperature reached before the occupied period.<br />

If both cool-down <strong>and</strong> purge mode or warm-up <strong>and</strong> purge mode operations are required, <strong>and</strong> the<br />

outdoor <strong>air</strong> is significantly hot <strong>and</strong> humid, or colder than the space <strong>air</strong> during the occupied period,<br />

then the purge operation must be performed first, <strong>and</strong> the cool-down or warm-up operation follows<br />

until the space temperature is maintained within predetermined limits. During purge mode, the minimum<br />

outdoor <strong>air</strong>, economizer, <strong>and</strong> exhaust dampers are opened 100 percent, <strong>and</strong> the recirculating<br />

damper is closed. During warm-up or cool-down mode, the minimum outdoor <strong>air</strong>, economizer, <strong>and</strong><br />

exhaust dampers are closed, <strong>and</strong> the recirculating damper is opened 100 percent.<br />

Only when the outdoor <strong>air</strong> can be used for free cooling, <strong>and</strong> to squeeze out the contaminated<br />

indoor <strong>air</strong> at the same time, are the cool-down <strong>and</strong> purge operations combined into a single<br />

operation.<br />

A steam humidifier is the most widely used humidifier when a warm <strong>air</strong> supply is required in winter in<br />

an AHU or PU. A humidity sensor is <strong>of</strong>ten located in the supply duct just after the supply fan discharge,<br />

to sense the relative humidity <strong>of</strong> the discharge <strong>air</strong>. The DDC controller receives the sensed signal <strong>and</strong><br />

positions the two-way valve to modulate the steam flow rate entering the steam humidifier, as shown in<br />

Figs. 15.42 <strong>and</strong> 15.43, until the relative humidity <strong>of</strong> the discharge <strong>air</strong> meets the required set point.<br />

When the fan is turned on, the humidifier control is energized. The steam valve closes when the<br />

fan is turned <strong>of</strong>f.<br />

If a steam humidifier is installed, it is critical that the humidifying capacity not be exceeded, so<br />

that a wet surface does not occur in the AHU as well as in the supply duct in order to maintain an<br />

acceptable indoor <strong>air</strong> quality.<br />

For <strong>air</strong> systems serving conditioned space that needed both close control <strong>of</strong> the space temperature<br />

<strong>and</strong> relative humidity with a sensible ratio <strong>of</strong> the space <strong>conditioning</strong> line SHR s above 0.9, a<br />

dew point control is <strong>of</strong>ten used. Dew point control involves using a water cooling coil, DX coil,<br />

or <strong>air</strong> washer to cause a specific amount <strong>of</strong> conditioned <strong>air</strong> to cool <strong>and</strong> dehumidify or occasionally<br />

cool <strong>and</strong> humidify to point cc, such as that on Fig. 23.10. Because <strong>of</strong> the high relative<br />

humidity <strong>of</strong> the departing <strong>air</strong>, the temperature T cc is approximately equal to the dew point on the<br />

saturation curve.<br />

When the indoor space temperature is to be maintained at 75°F (23.9°C), with a relative humidity<br />

<strong>of</strong> 50 percent, T cc � 55°F (12.8°C), � cc � 97 percent, <strong>and</strong> SHR s � 0.95, the state point <strong>of</strong> the<br />

conditioned space r must move approximately along the horizontal dew point line. Either the sensible<br />

cooling load is absorbed by the supply <strong>air</strong> or reheating is provided to the supply <strong>air</strong> by a reheating<br />

coil to compensate the sensible load at part load, if the space temperature is maintained at 75°F<br />

(23.9°C), the relative humidity must be at 50 percent. A temperature sensor senses the space temperature<br />

T r, <strong>and</strong> a DDC controller modulates the capacity <strong>of</strong> the reheating coil according to the<br />

sensed space temperature to maintain T r � 75°F (23.9°C) with � cc � 50 percent.<br />

Dew point control is simple <strong>and</strong> effective. Its main drawback is its need for reheating which<br />

wastes energy. Dew point control is mainly used for industrial applications such as clean rooms.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!