16.01.2013 Views

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

Handbook of air conditioning and refrigeration / Shan K

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

St<strong>air</strong> <strong>and</strong> Shaft Vents<br />

Zone Smoke Control<br />

AIR SYSTEMS: FAN COMBINATION AND SMOKE CONTROL 22.31<br />

st<strong>air</strong>well doors was lower than 0.25 in. WC (65 Pa) in summer <strong>and</strong> winter. During nonfire conditions,<br />

pressure differences were between 0.05 <strong>and</strong> 0.1 in. WC (13 <strong>and</strong> 25 Pa) across the st<strong>air</strong>well<br />

doors if there was a vent in the external wall on the second floor. When a building fire was simulated<br />

on the second floor, there was no smoke backflow from the fire floor through the st<strong>air</strong>well<br />

door when the st<strong>air</strong>well doors on the first <strong>and</strong> second floors were opened <strong>and</strong> the vent on the second<br />

floor external wall was also opened. Smoke backflow occurred when st<strong>air</strong>well doors on the first,<br />

second, <strong>and</strong> third floors were open.<br />

Overpressure Relief Vents. A relief vent is typically an assembly in which a fire damper is connected<br />

in series with a barometric damper. The barometric damper is normally closed. If the st<strong>air</strong>well<br />

is pressurized above a predetermined limit, the vents open <strong>and</strong> relieve <strong>air</strong> to various building floors. A<br />

counterweight in the barometric damper sets the maximum pressure limit. Fire dampers are normally<br />

closed, <strong>and</strong> open when the st<strong>air</strong>well pressurization system is turned on in case <strong>of</strong> a building fire.<br />

According to the experimental results <strong>of</strong> Tamura (1990b), the performance <strong>of</strong> the overpressure<br />

relief vents at a supply flow rate <strong>of</strong> 28,000 cfm (13,210 L/s) was slightly better than the performance<br />

<strong>of</strong> a ground-floor exit door at a supply flow rate <strong>of</strong> 17,800 cfm (8400 L/s). If supply flow<br />

rates are the same, the difference is further reduced.<br />

Fan Bypass. When the st<strong>air</strong>well is overpressurized, a pressure sensor located inside the st<strong>air</strong>well<br />

signals a feedback control to open a fan bypass damper so that part <strong>of</strong> the supply <strong>air</strong> returns to the<br />

centrifugal fan inlet, as shown in Fig. 22.7a. The <strong>air</strong> volume flow supplied to the st<strong>air</strong>well is reduced<br />

until the pressure at the pressure sensor drops below a preset value. If the pressure sensor is<br />

located on the ro<strong>of</strong>top or outdoors, it should be shielded from the influence <strong>of</strong> wind.<br />

Variable-Speed or Controllable-Pitch Fan. When excessive pressure is detected in the st<strong>air</strong>well,<br />

a controller actuates an adjustable-frequency variable-speed drive to reduce the speed <strong>of</strong> a centrifugal<br />

fan or to vary the blade pitch <strong>of</strong> a vane-axial fan to maintain the required pressure inside the<br />

st<strong>air</strong>well at the pressure sensor. The test results in Tamura (1990b) showed that both fan bypass <strong>and</strong><br />

variable-speed controls require a response time <strong>of</strong> more than 5 min. Variable-speed control is<br />

slightly faster. Because reliability is the primary factor in st<strong>air</strong>well pressurization control, <strong>and</strong> because<br />

<strong>of</strong> its very short operating period, it may not be worthwhile to install an expensive adjustablefrequency<br />

ac inverter to provide variable-speed control.<br />

ASHRAE/IESNA St<strong>and</strong>ard 90.1-1999 m<strong>and</strong>atorily specifies that st<strong>air</strong> <strong>and</strong> elevator shaft vents shall<br />

be equipped with motorized dampers which are automatically closed during normal building operation<br />

<strong>and</strong> are interlocked to open by fire <strong>and</strong> smoke control detection systems when required.<br />

Zone smoke control requires that a building be divided into a number <strong>of</strong> smoke control zones. The<br />

control zones are separated from one another by barriers, such as walls, floors, ceilings, <strong>and</strong> doors.<br />

In high-rise buildings, each floor is a separate zone, or it may be subdivided into many smoke control<br />

zones, or a smoke control zone consists <strong>of</strong> more than one floor.<br />

In case <strong>of</strong> a building fire, the spread <strong>of</strong> smoke from the zone <strong>of</strong> fire origin (the smoke zone)<br />

to adjacent zones is limited by pressure differences <strong>and</strong> <strong>air</strong>flows. The required pressure differential<br />

depends on the pressure produced by the fire gases, i.e., the temperature <strong>of</strong> the building fire. To<br />

form a pressure difference between the smoke zone <strong>and</strong> adjacent control zones, zone smoke<br />

control provides smoke exhaust on the fire floor (smoke zone) by opening the smoke damper<br />

connected to the smoke exhaust duct. At the same time, it supplies outdoor <strong>air</strong> to the floor or<br />

floors above <strong>and</strong> below the fire floor (to control zones adjacent to the smoke zone) <strong>and</strong> pressurizes

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!