SIMATIC S7 Ex Analog Modules<br />

Temperature range<br />

type J<br />

3-14<br />

Table 3-13 shows the representation of the digitized measured value for the<br />

temperature range, sensor type J.<br />

Table 3-13 Representation of the digitized measured value of an analog input<br />

module (temperature range, type J)<br />

Temperature<br />

range in C<br />

Decimal Hexadecimal Range<br />

> 1360.0 32767 7FFFH Overflow<br />

1360.0<br />

13600 3520H<br />

:<br />

:<br />

:<br />

Overrange<br />

1200.1<br />

12001 2EE1H<br />

1)<br />

1200.0<br />

12000 2EE0H<br />

:<br />

:<br />

:<br />

:<br />

:<br />

:<br />

Rated range<br />

-210.0<br />

-2100 F7CCH<br />

-210.1 -2101 F7CBH Underrange 1)<br />

In the case of incorrect wiring (e.g. polarity reversal, open inputs) or a sensor fault in<br />

the negative range (e.g. incorrect type of thermocouple), on dropping below F31CH<br />

the analog input module signals underflow and outputs 8000H .<br />

1) The characteristic of the thermocouple is not defined in the overrange and<br />

underrange. The rise of the characteristic curve is retained on leaving the linearized<br />

rated range. It is not possible to specify the accuracy of these ranges. It is not possible<br />

to specify the accuracy of these ranges.<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04