SIMATIC S7 HART Analog Modules<br />

Wiring diagram<br />

4-22<br />

SM 3 32<br />

AO 2 x 0/4...20mA HART<br />

Output 0<br />

Output 1<br />

X 2<br />

3 4<br />

332-5TB00-0AB0<br />

SF<br />

F0<br />

H0<br />

x<br />

<strong>II</strong> (2) G<br />

[EEx ib] <strong>II</strong>C<br />

F1<br />

H1<br />

Figure 3-18 shows the wiring diagram for the analog output module SM 332;<br />

AO 2 x 0/4...20mA HART. Detailed technical data for the analog output module<br />

can be found on the following pages.<br />

Logic and<br />

backplane<br />

bus<br />

interfacing<br />

H (0,1)<br />

Modem<br />

SF<br />

D A<br />

Digital / analog<br />

transformer<br />

L +<br />

M<br />

D A<br />

Modem<br />

F (0,1)<br />

L +<br />

M<br />

Galvanic isolation<br />

SF Group error indicator [red]<br />

F (0, 1) Channel-specific fault indication [red]<br />

H (0, 1) HART-status indication [green]<br />

390<br />

HART<br />

L +<br />

Isolation amplifier<br />

390<br />

HART<br />

Fig. 4-9 Module view and block diagram of SM 332; AO 2 x 0/4...20mA HART<br />

Notes on<br />

intrinsically-safe<br />

installation<br />

Power supply for<br />

an intrinsicallysafe<br />

structure<br />

Unswitched output<br />

channels<br />

50<br />

50<br />

M<br />

L+<br />

CH0<br />

0...650<br />

M<br />

CH1<br />

0...650<br />

L +<br />

QI 0<br />

M 0-<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

M<br />

CH0<br />

QI 1 CH1<br />

M 1-<br />

Section 4.3 provides you with a summary of infomation on intrinsically-safe<br />

installation. Detailed information can be found in Section 1.5.<br />

In order to maintain the clearances and creepage distances, L+ / M must be<br />

routed via the line chamber LK393 when operating modules with signal<br />

cables that lead to the hazardous location, see Section 1.2.<br />

To ensure that the unswitched output channels of the analog output module<br />

SM 332; AO 2 x 0/4...20mA HART are without current or voltage, you must<br />

deactivate them. You can deactivate an output channel in STEP 7 using the<br />

“Output” parameter block (see Section 4.4).