Structure of the<br />

parameter data<br />

records for HART<br />

analog output<br />

modules<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

Figure 4-11 shows data record 0 for the static parameters and data record 1<br />

for the dynamic parameters. In the case of S5 and the norm master, all the<br />

parameters are transferred to data record 0.<br />

7 6 5 4 3 2 1 0<br />

Parameter data record 0<br />

Byte 0 0 0 0 0 0 0 Group diagnostics<br />

Channel 0<br />

Channel 1<br />

Byte 1 0 0 0 0 0 0 0 0<br />

Byte 0<br />

Byte 2<br />

Byte 3<br />

Byte 4<br />

Byte 5<br />

7 6 5 4 3 2 1 0<br />

0 0 0 0 0 0 0<br />

Byte 1 0 0 0 0<br />

Byte 6<br />

to 9<br />

Byte 10<br />

to 13<br />

Enable diagnostic interrupt<br />

0 0<br />

must be 0<br />

must be 0<br />

Enables<br />

Channel 0<br />

Channel 1<br />

Behavior during CPU 2#00 = subst. value*<br />

STOP (OD active) 2#01 = last value<br />

M. type, m. range, channel 1<br />

M. type, m. range, channel 0<br />

see<br />

following<br />

Table 4-12<br />

Reserved<br />

Reserved<br />

Subst. value, channel 0<br />

Subst. value, channel 1<br />

Reserved<br />

Reserved<br />

Fig. 4-11 Parameters of the HART analog output module<br />

* For the substitute value -6912 (E500 Hex) the outputs will be disabled.<br />

Parameter data record 1<br />

First “High-<br />

Byte,” then<br />

“Low-Byte”<br />

Table 4-12 Codes for the output type and output range for HART analog output<br />

modules<br />

Output type Code Output range Code<br />

Deactivated 2#0000 Deactivated 2#0000<br />

Current output<br />

without HART<br />

Current output<br />

with HART<br />

2#0010 0 to 20 mA<br />

4 to 20 mA<br />

SIMATIC S7 HART Analog Modules<br />

2#0111 4 to 20 mA HART<br />

All commands permitted,<br />

and monodrop operation.<br />

2#0010<br />

2#0011<br />

2#1100<br />