Safety Standards, FM Approval<br />

Safety standards<br />

used<br />

B-2<br />

The following safety standards apply to all EX modules:<br />

EN50014 (1977 + A1 .. A5):<br />

Electrical equipment for hazardous locations:<br />

General specifications.<br />

EN50020 (1977 + A1.. A5):<br />

Electrical equipment for hazardous locations:<br />

Intrinsic safety ”i”.<br />

DIN EN 61010 (Teil 1 v. 3/94):<br />

Section 6.3.1 and Appendix D.2 Table D.6<br />

Safety requirements for electrical measuring, control and laboratory<br />

equipment.<br />

DIN EN 61131 (Teil 2 v. 5/95):<br />

Programmable logic controllers, operational equipment requirements and<br />

testing.<br />

DIN EN 60204 (Teil 1 v. 6/93):<br />

Electrical equipment of machines:<br />

General requirements.<br />

The designations of safety characteristic values have been adapted in the<br />

course of harmonization of the standards EN50012 .. EN50020. The most<br />

important characteristic data for the relevant operational equipment are<br />

assigned as follows:<br />

Uo, Umax, Ua Uo Maximum output voltage<br />

Io, Ia, Ik Io Maximum output current<br />

Um Um Maximum r.m.s. power-frequency<br />

voltage or maximum direct voltage<br />

Co, Ca Co Maximum external capacitance<br />

Lo, La Lo Maximum external inductance<br />

P, Pmax Po Maximum output power<br />

C, Ci Ci Maximum internal capacitance<br />

L, Li Li Maximum internal inductance<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04