Special feature of<br />

resistant<br />

measurement<br />

Non-connected<br />

input channels<br />

Adjustable types<br />

of measurement<br />

Adjustable<br />

measuring ranges<br />

Wire break check<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

Only one channel per channel group is required for resistance measurement.<br />

The ”2nd” channel of the group is used for current injection (IC).<br />

The measured value is obtained on accessing the ”1st” channel of the group.<br />

The ”2nd” channel of the group is preset with the overflow value ”7FFFH”.<br />

During diagnostics, the 1st channel provides the actual status (in compliance<br />

with parameterization) and the 2nd channel ”faultless”.<br />

Activated and non-connected channels of the analog input module SM 331;<br />

AI 8 x TC/4 x RTD must be short-circuited to ensure optimum interference<br />

immunity for the analog input module. The non-connected channels should<br />

also be deactivated in STEP 7 (see Section 3.6.3) in order to shorten the<br />

module cycle time.<br />

The following types of measurement can be set on the analog input module<br />

SM 331; AI 8 x TC/4 x RTD. The measurement mode is set in STEP 7 (see<br />

Section 3.6.3).<br />

Voltage measurement<br />

Resistance measurement<br />

Temperature measurement<br />

The measuring ranges, for which you can use the analog input module<br />

SM 331; AI 8 x TC/4 x RTD are specified in the Tables 3-32 to 3-34. You can<br />

set the required measuring ranges in STEP 7 (see Section 3.6.3).<br />

The analog input module SM 331; AI 8 x TC/4 x RTD carries out an wire<br />

break check, provided it is enabled by means of parameterization, for all<br />

areas. All 4 terminal wires are monitored for wire break in resistance<br />

thermometer mode (RTD).<br />

Measuring ranges Table 3-32 contains all measuring ranges for voltage measurements.<br />

for voltage<br />

measurement<br />

Table 3-32 Measuring ranges for voltage measurement<br />

Selected measurement<br />

mode<br />

Voltage The digitized analog values are specified in Section<br />

3.1.2 in Table 3-3 Voltage measuring ranges<br />

SIMATIC S7 Ex Analog Modules<br />

Explanation Measuring range<br />

25 mV<br />

50 mV<br />

80 mV<br />

250 mV<br />

500 mV<br />

1 V<br />

3-57