SM 332; AO 2 x 0/4...20mA HART<br />

Dimensions and weight<br />

Dimensions W x H x D (mm) 40 x 125 x 120<br />

Weight approx. 280 g<br />

Module-specific data<br />

Number of outputs 2<br />

Line length, shielded max. 400 m<br />

Type of protection KEMA<br />

(see Appendix A)<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

[EEx ib] <strong>II</strong>C to<br />

EN 50020<br />

Test number KEMA 98 ATEX2359 X<br />

Voltages, currents, potentials<br />

Bus power supply<br />

Rated load voltage<br />

Reverse voltage protection<br />

Galvanic isolation<br />

Between channels and<br />

backplane bus<br />

yes<br />

Between channels yes<br />

Between channels and load<br />

voltage L+<br />

yes<br />

Between backplane bus<br />

and load voltage L+<br />

yes<br />

5 V DC<br />

24 V DC<br />

yes<br />

Permissible difference in potential (UISO) for signals<br />

from a hazardous area<br />

Between channels and<br />

backplane bus<br />

Between channels and load<br />

voltage L+<br />

60 V DC<br />

30 V AC<br />

60 V DC<br />

30 V AC<br />

Between channels 60 V DC<br />

30 V AC<br />

Between backplane bus<br />

and load voltage L+<br />

60 V DC<br />

30 V AC<br />

Voltages, currents, potentials continued<br />

Permissible difference in potential (UISO) for signals<br />

from non-hazardous area<br />

Between channels and 400 V DC<br />

backplane bus<br />

250 V AC<br />

Between channels and 400 V DC<br />

load voltage L+ 250 V AC<br />

Between channels 400 V DC<br />

250 V AC<br />

Between backplane bus 75 V DC<br />

and load voltage L+ 60 V AC<br />

Insulation tested<br />

Channels to backplane<br />

bus and load voltage L+<br />

with 1500 V AC<br />

Channels to each other with 1500 V AC<br />

Between backplane bus<br />

and load voltage L+<br />

with 500 V DC<br />

Channels shielded with 500 V DC<br />

Current input<br />

<br />

<br />

From backplane bus<br />

From load voltage L +<br />

(at rated data)<br />

max. 100 mA<br />

max. 150 mA<br />

Module power loss<br />

Analog value formation<br />

typically 3.5 W<br />

Output value<br />

SIMATIC S7 HART Analog Modules<br />

Resolution (incl. overrange)<br />

Readback value<br />

12 bit (+ polarity)<br />

8 bit<br />

Cycle time (all channels)<br />

Settling time<br />

5 ms<br />

for resistive load 2.5 ms<br />

for inductive load 2.5 ms<br />

for capacitive load 4 ms<br />

Switch substitute values<br />

Readback value<br />

yes, configurable<br />

Resolution<br />

8 bit (+ polarity)<br />

Conversion time (per channel)<br />

40 ms<br />

4-23