1-38<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

Fig. 1-17 Lightning/overvoltage protection for a gas compressor station<br />

1<br />

2<br />

3<br />

4<br />

Protective device for AC power system<br />

Protective device for measurement and control systems<br />

Spark gap<br />

Protective device, required for high–cost measurement and control equipment<br />

Protective device, not required for shielded cables and<br />

low–cost measurement and control equipment<br />

Protective device, not required for equipment with high electric strength<br />

Protective device, not required with suitable system shielding<br />

45 o<br />

Control room<br />

(shielded)<br />

Low M&C<br />

voltage cabinet<br />

system<br />

Control console<br />

EB<br />

Annex<br />

M&C equipment<br />

Sub-distribution<br />

board<br />

Insulating<br />

flange<br />

Station ground<br />

Cable duct (shielded)<br />

2<br />

1<br />

3<br />

M<br />

Metal<br />

conduit<br />

Cable racks as EB ring<br />

Light fixture<br />

EB<br />

Insulation<br />

Smoke detector<br />

Compressor bay<br />

(shielded)<br />

M<br />

Fig. 1-17 ”Lightning/overvoltage protection for a gas compressor station”<br />

shows an example of how protective devices can be used.<br />

1.9.6 Example of Lightning and Overvoltage Protection<br />

Mechanical Configuration of an Automation System with SIMATIC S7 Ex Modules