SIMATIC S7 HART Analog Modules<br />
Analog values and<br />
resolution<br />
4-16<br />
The representation of the analog values is the same as for the analog input<br />
module SM 331; AI 4 x 0/4...20mA, see Section 3.1.2. The resolution of the<br />
measured value is directly dependent on the selected integration time, i.e. the<br />
greater the integration time selected for an analog input channel, the more<br />
precise the resolution of the measured value.<br />
10 bits + polarity (integration time 2.5 ms)<br />
13 bits + polarity (integration time 16.6/ 20 ms)<br />
15 bits + polarity (integration time 100 ms)<br />
Table 4-9 Output range of the analog input modules SM 331; AI 2 x 0/4...20 mA HART<br />
Selected output type Explanation Output range<br />
Current The digitalized analog values can be found in part 3.1.2 in Table<br />
3-4 of the current measuring range.<br />
Integration times<br />
when HART is<br />
used<br />
Default settings<br />
Wire break<br />
monitoring<br />
Inserting and<br />
removing modules<br />
Operation with<br />
standard master<br />
0 to 20 mA<br />
4 to 20 mA<br />
If you use measuring transducers with the HART protocol, it is advisable to<br />
assign integration times of 16.6, 20 or 100 ms, in order to minimize the<br />
influence of the modulating alternating current on the measuring signal.<br />
The HART measurement mode is set as default. There are other default<br />
settings for integration time, diagnostics, interrupts (see Table 4-4). The<br />
HART analog module uses these settings, unless you modify them using<br />
STEP 7.<br />
Wire break monitoring is not possible for the current range 0 to 20 mA.<br />
For the current range 4 to 20 mA, if the input current falls below I3.6<br />
mA this is interpreted as a wire break and a diagnostic interrupt is<br />
triggered (provided the interrupt is enabled).<br />
The HART analog modules support the function “Change modules during<br />
operation.” However, it is only possible to evaluate the insert / remove<br />
module interrupts with a S7/M7 400 CPU master and an active backplane bus<br />
in the ET 200M.<br />
Information on operating the modules in a distributed configuration with a<br />
standard master can be found in manual /140/. The manual lists the<br />
differences to be taken into consideration if you are operating the modules<br />
with a S7/M7 DP master and a standard master (for example, IM 308C with<br />
S5).<br />
Parameter assignment with COM PROFIBUS (.GSE file or type file<br />
required)<br />
Restricted evaluation when inserting or removing modules.<br />
I/O Modules with Intrinsically-Safe Signals<br />
C79000-G7076-C152-04