SIMATIC S7 HART Analog Modules<br />

Analog values and<br />

resolution<br />

4-16<br />

The representation of the analog values is the same as for the analog input<br />

module SM 331; AI 4 x 0/4...20mA, see Section 3.1.2. The resolution of the<br />

measured value is directly dependent on the selected integration time, i.e. the<br />

greater the integration time selected for an analog input channel, the more<br />

precise the resolution of the measured value.<br />

10 bits + polarity (integration time 2.5 ms)<br />

13 bits + polarity (integration time 16.6/ 20 ms)<br />

15 bits + polarity (integration time 100 ms)<br />

Table 4-9 Output range of the analog input modules SM 331; AI 2 x 0/4...20 mA HART<br />

Selected output type Explanation Output range<br />

Current The digitalized analog values can be found in part 3.1.2 in Table<br />

3-4 of the current measuring range.<br />

Integration times<br />

when HART is<br />

used<br />

Default settings<br />

Wire break<br />

monitoring<br />

Inserting and<br />

removing modules<br />

Operation with<br />

standard master<br />

0 to 20 mA<br />

4 to 20 mA<br />

If you use measuring transducers with the HART protocol, it is advisable to<br />

assign integration times of 16.6, 20 or 100 ms, in order to minimize the<br />

influence of the modulating alternating current on the measuring signal.<br />

The HART measurement mode is set as default. There are other default<br />

settings for integration time, diagnostics, interrupts (see Table 4-4). The<br />

HART analog module uses these settings, unless you modify them using<br />

STEP 7.<br />

Wire break monitoring is not possible for the current range 0 to 20 mA.<br />

For the current range 4 to 20 mA, if the input current falls below I3.6<br />

mA this is interpreted as a wire break and a diagnostic interrupt is<br />

triggered (provided the interrupt is enabled).<br />

The HART analog modules support the function “Change modules during<br />

operation.” However, it is only possible to evaluate the insert / remove<br />

module interrupts with a S7/M7 400 CPU master and an active backplane bus<br />

in the ET 200M.<br />

Information on operating the modules in a distributed configuration with a<br />

standard master can be found in manual /140/. The manual lists the<br />

differences to be taken into consideration if you are operating the modules<br />

with a S7/M7 DP master and a standard master (for example, IM 308C with<br />

S5).<br />

Parameter assignment with COM PROFIBUS (.GSE file or type file<br />

required)<br />

Restricted evaluation when inserting or removing modules.<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04