Mechanical Configuration of an Automation System with SIMATIC S7 Ex Modules<br />

Table 1-8 Working on systems to type of protection: EEx de [ib] T5 .. T6<br />

Type of<br />

protection of<br />

apparatus used in<br />

system<br />

1-44<br />

Type of work to<br />

be carried out<br />

EEx ib Zone 1 Zone 2<br />

Opening the<br />

housing, Ex i/e<br />

housing only<br />

Connecting/<br />

disconnecting<br />

lines<br />

Current, voltage<br />

and resistance<br />

measurement<br />

Work within Additional<br />

requirements and<br />

notes<br />

Allowed Allowed If no other<br />

apparatus is in the<br />

housing<br />

Allowed Allowed<br />

Allowed with<br />

certified apparatus<br />

Allowed<br />

Soldering Prohibited Allowed if<br />

soldering<br />

temperature lower<br />

than ignition<br />

temperature<br />

EEx e Zone 1 Zone 2<br />

Opening the<br />

housing, Ex i/e<br />

housing only<br />

Connecting/<br />

disconnecting<br />

lines<br />

Current, voltage<br />

and resistance<br />

measurement<br />

Allowed Allowed If no other<br />

apparatus is in the<br />

housing<br />

Not allowed<br />

unless in<br />

de-energized state<br />

Voltage<br />

measurement with<br />

certified apparatus<br />

only<br />

Only in<br />

de-energized state<br />

and if no risk of<br />

explosion<br />

Voltage<br />

measurement with<br />

certified apparatus<br />

only<br />

Soldering Prohibited Allowed in<br />

de-energized state<br />

if soldering<br />

temperature lower<br />

than ignition<br />

temperature<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04